| Powerware 9305 | |
| Operational | |
| Nominal input voltage (Vac) | 220/380, 230/400, 240/415 Vac three-phase |
| Input voltage range | 170/294
to 279/484 Vac (7.5/10/15 kVA); 170/294 to 275/476 Vac (20/30 kVA); 170/294 to 279/484 Vac (40/50 kVA); 180/312 to 279/484 Vac (60 kVA) |
| Operating frequency | 50/60 Hz (45 to 65 Hz) |
| Input power factor | 0.96 |
| Input power factor | 10% THDi with input filter |
| Nominal output voltage | 220/380, 230/400, 240/415 Vac three-phase |
| Output voltage regulation | ±1% static, 100%
unbalanced load accepted; ±5% dynamic at 100% load change, <1 ms recovery time |
| Overload capacity | Inverter 150% for 30 sec; 170% for 5 sec |
| Efficiency | Up to 94% online |
| User interface | |
| LCD display | Multilingual LCD display showing measurements of performance and alarms (View UPS optional with 7.5/10/15 kVA models) |
| LED | UPS On, On battery, On bypass, Alarm(7.5/10/15 kVA models also On line, Overtemperature, Service; additionally 4 LEDs for load bar and overload) |
| Standard communication ports | 2xRS232 for local support, one with modem support;4xrelay contacts: UPS OK/Alarm, Line failure, Low battery, UPS bypassed;4xprogrammable inputs: Generator on, External bypass, Inverter on/off, Environment alarm; 1xEmergency power off input |
| Options | Long life 10y battery cabinets Input filter cabinets Isolation transformer cabinets Hot Sync™ parallel systems ConnectUPS SNMP adapter ViewUPS remote LCD panel |
| Environmental | |
| Operating Temperature | 0°C to +40°C |
| Storage Temp |
-25°C to +40°C |
| Altitude |
< 1000 M |
| Audible Noise | <45 dB (7.5/10/15 kVA) <50 dB (20/30 kVA) <55 dB (40/50/60 kVA) |
| Certification | |
| Quality | ISO 9001 |
| Markings | CE / GOST |
| Safety | EN 50091-1-1: 1996; IEC 60950 |
| EMC | EN 50091-2: 1995 |