Eaton Logo, links to the Eaton homepage

Powerware 5125 Rackmount UPS Technical Specs

Battery Runtimes
Powerware 5125
Rating  6000 VA
Part number  103003612-5591
Capacity (VA/watts)  6000/5400
Dimensions WxDxH (mm)  445x661x133
Weight (kg)  73
Input connection  IEC309/ 32A 
Output connection  IEC309 32A plug
(4)IEC320 16A (4) IEC320 10A
Typical runtime (Full load) pf 0,9 5 min
  (Half load) 15 min
Operational
Nominal input voltage (Vac)  220/230/240 Vac 
Input voltage range  166-276 VAC (+20/-30% of nominal) 
Operating frequency  50/60 Hz auto sensing 
Input power factor  Same as load 
Nominal output voltage   220/230/240 Vac 
Output voltage regulation -10%/+6% of selected nominal voltage 
Overload capacity  110% 3 min; 150% 10 cycles 
Efficiency 95%
User interface
LED  Informative LED display 
Standard communication ports   RS232
Optional  SNMP/WEB card
Environmental
 Operating Temperature 0°C to +40°C 
 Storage Temp -15°C to +55°C
 Altitude < 3000 M
 Audible Noise  < 45 dB normal mode
<50 dB battery mode
Certification
Markings  CE/UL (1000-1500 VA), CE (3000 & 6000 VA) 
Safety  EN 50091-1-1 & UL 1778 (1000-1500 VA), EN50091-1-1 (3000 & 6000 VA)
EMC  EN 50091-2, EN 6100-3-2 (1000 - 3000 VA)
Battery cabinets
Battery cabinets PW5125RM 484 V EBM for PW5125RM 1000/1500 VA
PW5125RM 120 V EBM for PW5125RM 3000 VA

Go to top

Powerware 5125 Battery Run Time Chart (in minutes)

Load VA / W 6000 VA
500 VA / 450 W 100 (300)
1000 VA / 900 W 59 (140)
1500 VA / 1350 W 35 (100)
2000 VA / 1800 W  26 (79)
3000 VA / 2700 W  15 (49)
4000 VA / 3600 W 10 (35)
5000 VA / 4500 W 7 (24)
6000 VA / 5400 W 5 (19)

* Run time chart provides typical information. Battery run times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

E-mail this page Print this page