Eaton Logo, links to the Eaton homepage

Powerware 5115 UPS Technical Specs

Battery Runtimes
 
Powerware 5115
Rating 500 VA   750 VA 1000 VA 1400 VA
Part number  05146549-5591  05146555-5591  05146561-5591  05146567-5591
Capacity (VA/Watts)  500/320   750/500 1000/670  1400/950
Dimensions WxDxH (mm)  150x268x185  150x333x185  150x333x185  150x388x185
Weight (kg)  8 12 13 17
Input connection  IEC320/ 10A 
Output connection  4xIEC320 10A
Typical runtime (Full load) 5 min  6 min 5 min 5 min 
Typical runtime (Half load) 15 min 17 min 15 min  15 min
Operational
Nominal input voltage (Vac)  220/230/240 Vac 
Input voltage range  184-276 VAC (+/-20% of nominal)   
Operating frequency  50/60 Hz auto sensing
Input power factor  Same as load  
Nominal output voltage   220/230/240 Vac
Output voltage regulation -10%/+6% of selected nominal Voltage
Overload capacity  110% 3 min; 150% 10 cycles 
Efficiency 95%
User interface
LED  Four LEDs; UPS on, UPS on battery, overload, alarm 
Standard communication ports   RS232
Optional  External SNMP adapter
Environmental
 Operating Temperature 0°C to 40°C 
 Storage Temp -15°C to 55°C
 Altitude < 3000 M
 Audible Noise  < 40 dB
Certification
Markings  CE/GS/UL 
Safety  EN 50091-1-1 & UL 1778 
EMC  EN 50091-2, EN6100-3-2

Go to top

Battery Run Times (in minutes)

Load PW5115 500(i) PW5115 750(i) PW5115 1000(i) PW 5115 1400(i)
200 VA / 128 W 17 38 41 58
300 VA / 192 W 11 27 28 41
500 VA / 320 W 5 14 15 28
600 VA / 402 W10 9 10 19
750 VA / 503 W   6 8 14
900 VA / 603 W 6 10
1000 VA / 670 W     5 8
1200 VA / 804 W 6
1400 VA / 938 W       5

*This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.

E-mail this page Print this page
Copyright ©2008 Eaton Corporation.
All rights reserved.