Components |
| Fully rated, disc-type
SCR |
| Mimic panel LED current flow |
| Backlit LCD graphical
display |
| Dual-redundant fans |
| Triple-redundant power
supplies |
| Dual-redundant internal bus |
| TVSS 80 kA (std.), 160
kA (opt.) |
|
Communications and Software |
| Password protection-defined user tiers |
| Remote access |
RS232, RS485 and Web-based |
| Event types |
information, warnings and alarms |
| Alarm notification |
email or email to pager |
| Remote-downloadable software upgrades |
| Emergency power off:
remote (std.), local (opt.) |
| Five relay contacts (std.) |
|
Power and Event Management |
| Metering 1 |
kVA, kW, Ipeak, phase, current, voltage, frequency |
| Metering 2 |
power factor, kVA demand, harmonic
analyzer |
| Event alarm log, 2,500 events |
|
Electrical Characteristics |
| Voltage/frequency |
208/480/600V, 3 Phase, 4 Wire, 60Hz |
| Current rating |
200/400/600/800A |
| Short-circuit
withstand |
100 kA |
| Overload capability |
125% (30 min.), 150% (1
min.), 1000% (3 cycles) |
| Circuit breakers |
non-automatic or automatic |
|
Operational Characteristics |
| Full-digital controls |
| Type II fuse-less current path |
| System-assisted
bypass |
| PQ states |
preferred, acceptable and emergency |
| Automatic or manual
transfer |
| Sensing time |
2 ms |
| Auto transfer |
4 ms (or
less) |
| Reacquisition |
3 cycles |
| User-defined transfer
angle |
max 180° |
| Temperature |
0-40°C (operating), 0-80°C
(storage) |
| Audible noise |
<65 dBA
(6 ft.) |
|
Standards |
| All applicable NEMA
standards |
| UL 1008 listed |
| FCC compliant (Part
15) |
| NEC 2002 |
| ANSI/NFPA 70 (2002) |
| IEEE 587 (ANSI C62.41) |