Eaton Logo, links to the Eaton homepage

Powerware FERRUPS Tower UPS 60 Hz Technical Specs

Model Selection Guide
50 Hz Specs
60 Hz Rackmount Specs
Operation
Part No. FE
500
VA
FE
700
VA
FE
850
VA
FE
1.15
kVA
FE
1.4
kVA
FE
1.8
kVA
FE
2.1
kVA
FE
3.1
kVA
FE
4.3
kVA
FE
5.3
kVA
FE
7k
VA
FE
10k
VA
FE
12.5
kVA
FE
18
kVA
Nominal Input Voltage 120/208/240 208/240
Input Voltage Range +15%, -20%
Input Power Factor .98
Nominal Output Voltage 120/208/240
Output Voltage Regulation ±3% for input voltages +15% to -20% 
Output Voltage Waveform
Output Voltage THD
Sine Wave

6% or less at rated kW load
Overload Capacity 150% surge and 125% for 10 minutes on-line. 150% surge and 110% for 10 minutes on inverter.
Transfer Time 0 ms
Lightning, Surge, and Noise Protection 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests.
Common Mode ->120 dB.Normal Mode ->60dB
Efficiency %  85 86 85 88 88 90 90 91 90 90 90 90 91 92
Safety Certification UL,CSA (cUL)
EMI Compliance FCC Class A
Testing Standards ANSI/EEE C62.41 (1980);ANSI/EEE C62.45 (1987);IEC 801-2,801-4,801-5
Communication RS-232 serial port (DB-25),plus contact closures
Environmental
Operating Temperature 0 to 40°C
Storage Temperature -20° to +60° C 
Relative Humidity 5 to 95% without condensation
Audible Noise (dBA) 41 41 47 49 49 51 51 51 50 51 52 55 56 57
Altitude 3050 m (10,000 ft.) maximum
Model Guide 500 VA 700 VA 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA
Part No. FE
500 VA
FE
700 VA
FE
850 VA
FE
1.15 kVA
FE
1.4 kVA
FE
1.8 kVA
FE
2.1 kVA
FE
3.1 kVA
FE
4.3 kVA
FE
5.3 kVA
FE
7 kVA
FE
10 kVA
FE
12.5 kVA
FE
18 kVA
Capacity (kVA/kW) .5/.35 .7/.5 .85/.6 1.15/.8 1.4/1 1.8/1.25 2.1/1.5 3.1/2.2 4.3/3 5.3/3.7 7/5 10/7.5 12.5/10 18/15
Dimensions
HxWxD
inches
mm
12x10x21.25
305x255x540
15.1x15.2x20.2
385x390x515
21.2x15.25x22.9
540x390x585
29.5x15.5x25
750x395x635
36.5x19x32
930x485x815
Dimensions are for the UPS only on 10-18kVA (does not include battery pack)
Weight  lb
KG
62
28
79
36
85
39
132
60
154
70
183
83
196
89
256
116
359
163
505
229
604
274
875
397
1089
494
1362
589
Input Connection 6ft Cord w/NEMA 5-15P* 6ft Cord
w/NEMA
5-20P*
6ftCord
w/NEMA
L5-30P*
120 V/40 A
208 V/25 A
240 V/20 A
120 V/40 A
208 V/30 A
240 V/25 A
120 V/40 A
208 V/40 A
240 V/35 A

208 V/60 A
240 V/50 A

208 V/75 A
240 V/65 A

208 V/115 A
240 V/100 A
Output Connection (quantity)
(type)
4
NEMA 5-15R
6
NEMA 5-15R
6
NEMA 5-15R
  Hardwired output is standard. 
Contact Factory for receptacle options
Typical Runtime: (minutes) Full load

Half load
9

25
14

35
11

28
18

48
14

37
11

30
9

25
14

35
8

20
20

50
12

33
11

26
18

48
10

26

Go to top