| Operation |
| Part
No. |
QFE
500 VA |
QFE
700 VA |
QFE
850 VA |
QFE
1.15 kVA |
QFE
1.4 kVA |
QFE
1.8 kVA |
QFE
2.1 kVA |
QFE
3.1 kVA |
QFE
4.3 kVA |
QFE
5.3 kVA |
QFE
7 kVA |
QFE
10 kVA |
QFE
12.5 kVA |
QFE
18 kVA |
| Nominal
Input Voltage |
220/230/240 |
| Input
Voltage Range |
+15%,
-20% |
| Operating
Frequency |
50 Hz Nominal (adjustable limits +_0.01 Hz to +_3 Hz |
| Nominal
Output Voltage |
220/230/240 |
| Output
Voltage Regulation |
±3% for input voltages
+15% to -20% |
Output
Voltage Waveform
Output Voltage THD |
Sine
Wave
6%or less at rated kW load |
| Overload
Capacity |
150% surge and 125% for 10 minutes on-line. 150% surge and 110% for 10 minutes on inverter. |
| Transfer
Time |
0
ms |
| Lightning, Surge, and Noise Protection |
2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests.
Common Mode ->120 dB.Normal Mode ->60dB |
| Efficiency
% |
85 |
86 |
85 |
88 |
88 |
90 |
90 |
91 |
90 |
90 |
90 |
90 |
91 |
92 |
| Safety
Certification |
UL 1778,CSA
(cUL),GS (TUV),Complies with European Low Voltage Directive 73/23/EEC |
| EMI
Compliance |
FCC Class A, Complies with European Electromagnetic Compatibility Directive 89/336/EEC |
| Testing
Standards |
ANSI/EEE C62.41
(1980);ANSI/EEE C62.45 (1987);IEC 801-2,801-4,801-5
EN 50081-1,EN 500082-1,EN 500091-1,EN 500091-2,EN60950 |
| Communication |
RS-232 serial port (DB-25),plus contact closures |
| Environmental |
| Operating
Temperature |
0
to 40°C |
| Storage
Temperature |
-20° to +60° C |
| Relative
Humidity |
0
to 95% without condensation |
| Audible Noise
(dBA) |
41 |
41 |
47 |
49 |
49 |
51 |
51 |
51 |
50 |
51 |
52 |
55 |
56 |
57 |
| Altitude |
3050 m (10,000 ft.) maximum |
| Model
Guide |
500 VA |
700 VA |
850 VA |
1.15 kVA |
1.4 kVA |
1.8 kVA |
2.1 kVA |
3.1 kVA |
4.3 kVA |
5.3 kVA |
7 kVA |
10 kVA |
12.5 kVA |
18 kVA |
| Part
No. |
QFE
500 VA |
QFE
700 VA |
QFE
850 VA |
QFE
1.15 kVA |
QFE
1.4 kVA |
QFE
1.8 kVA |
QFE
2.1 kVA |
QFE
3.1 kVA |
QFE
4.3 kVA |
QFE
5.3 kVA |
QFE
7 kVA |
QFE
10 kVA |
QFE
12.5 kVA |
QFE
18 kVA |
| Capacity
(kVA/kW) |
.5/.35 |
.7/.5 |
.85/.6 |
1.15/.8 |
1.4/1 |
1.8/1.25 |
2.1/1.5 |
3.1/2.2 |
4.3/3 |
5.3/3.7 |
7/5 |
10/7.5 |
12.5/10 |
18/15 |
Dimensions
HxWxD |
inches
mm |
12x10x21.25
305x255x540 |
15.1x15.2x20.2
385x390x515 |
21.2x15.25x22.9
540x390x585 |
29.5x15.5x25
750x395x635 |
36.5x19x32
930x485x815
Dimensions are for the UPS only on 10-18 kVA (does not include
battery pack) |
| Weight |
lb
KG |
62
28 |
80
36 |
86
39 |
132
60 |
154
70 |
183
83 |
196
89 |
256
116 |
360
163 |
505
229 |
605
274 |
875
397 |
1341
609 |
1300
589 |
| Input Connection
|
IEC-320 (10A)male connector |
IEC-320
(16A)Mule
Connector |
220/19A
230/18A
240/17A |
220/21A
230/20A
240/19A |
220/27A
230/26A
240/24A |
220/43A
230/41A
240/39A |
220/43A
230/41A
240/39A |
220/81A
230/78A
240/75A |
| Output
Connection |
(quantity)
(type) |
4
IEC-320 (10A)male connector |
Hardwired
output is standard.
Contact Factory for receptacle options |
| Typical
Runtime: (minutes) |
Full
load
Half load |
9
25 |
14
35 |
11
28 |
18
48 |
14
37 |
11
30 |
9
25 |
14
35 |
8
20 |
20
50 |
12
33 |
11
26 |
18
48 |
10
26 |