Eaton Logo, links to the Eaton homepage

Powerware FERRUPS Tower UPS 50HZ Technical Specs

Model Selection Guide
60HZ Specs
60HZ rackmount Specs
Operation
Part No. QFE
500 VA
QFE
700 VA
QFE
850 VA
QFE
1.15 kVA
QFE
1.4 kVA
QFE
1.8 kVA
QFE
2.1 kVA
QFE
3.1 kVA
QFE
4.3 kVA
QFE
5.3 kVA
QFE
7 kVA
QFE
10 kVA
QFE
12.5 kVA
QFE
18 kVA
Nominal Input Voltage 220/230/240
Input Voltage Range +15%, -20%
Operating Frequency 50 Hz Nominal (adjustable limits +_0.01 Hz to +_3 Hz
Nominal Output Voltage 220/230/240
Output Voltage Regulation ±3% for input voltages +15% to -20% 
Output Voltage Waveform
Output Voltage THD
Sine Wave

6%or less at rated kW load
Overload Capacity 150% surge and 125% for 10 minutes on-line. 150% surge and 110% for 10 minutes on inverter.
Transfer Time 0 ms
Lightning, Surge, and Noise Protection 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests.
Common Mode ->120 dB.Normal Mode ->60dB
Efficiency %  85 86 85 88 88 90 90 91 90 90 90 90 91 92
Safety Certification UL 1778,CSA (cUL),GS (TUV),Complies with European Low Voltage Directive 73/23/EEC
EMI Compliance FCC Class A, Complies with European Electromagnetic Compatibility Directive 89/336/EEC
Testing Standards ANSI/EEE C62.41 (1980);ANSI/EEE C62.45 (1987);IEC 801-2,801-4,801-5
EN 50081-1,EN 500082-1,EN 500091-1,EN 500091-2,EN60950
Communication RS-232 serial port (DB-25),plus contact closures
Environmental
Operating Temperature 0 to 40°C
Storage Temperature -20° to +60° C 
Relative Humidity 0 to 95% without condensation
Audible Noise (dBA) 41 41 47 49 49 51 51 51 50 51 52 55 56 57
Altitude 3050 m (10,000 ft.) maximum
Model Guide 500 VA 700 VA 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA
Part No. QFE
500 VA
QFE
700 VA
QFE
850 VA
QFE
1.15 kVA
QFE
1.4 kVA
QFE
1.8 kVA
QFE
2.1 kVA
QFE
3.1 kVA
QFE
4.3 kVA
QFE
5.3 kVA
QFE
7 kVA
QFE
10 kVA
QFE
12.5 kVA
QFE
18 kVA
Capacity (kVA/kW) .5/.35 .7/.5 .85/.6 1.15/.8 1.4/1 1.8/1.25 2.1/1.5 3.1/2.2 4.3/3 5.3/3.7 7/5 10/7.5 12.5/10 18/15
Dimensions
HxWxD
inches
mm
12x10x21.25
305x255x540
15.1x15.2x20.2
385x390x515
21.2x15.25x22.9
540x390x585
29.5x15.5x25
750x395x635
36.5x19x32
930x485x815
Dimensions are for the UPS only on 10-18 kVA (does not include battery pack)
Weight  lb
KG
62
28
80
36
86
39
132
60
154
70
183
83
196
89
256
116
360
163
505
229
605
274
875
397
1341
609
1300
589
Input Connection IEC-320 (10A)male connector IEC-320
(16A)Mule
Connector
220/19A
230/18A
240/17A
220/21A
230/20A
240/19A
220/27A
230/26A
240/24A
220/43A
230/41A
240/39A
220/43A
230/41A
240/39A
220/81A
230/78A
240/75A
Output Connection (quantity)
(type)
4
IEC-320 (10A)male connector
  Hardwired output is standard. 
Contact Factory for receptacle options
Typical Runtime: (minutes) Full load

Half load
9

25
14

35
11

28
18

48
14

37
11

30
9

25
14

35
8

20
20

50
12

33
11

26
18

48
10

26

Go to top

E-mail this page Print this page
Copyright ©2008 Eaton Corporation.
All rights reserved.