| General Characteristics | ||
| Power Rating | 12 kW per UPS Module | |
| Efficiency | Up to 97% | |
| Heat Dissipation | <371W/1266 BTU/hr. at 100% rated load | |
| Cooling | Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust | |
| Audible Noise, Normal Operation | 58 dBA at 1 meter | |
| Altitude | 1000 meters (3300 ft. ASL) | |
| Input Characteristics | ||
| Input Voltage | 208 Vac and 400 Vac models | |
| Voltage Range |
208V model: 180 to 255 Vac 400V model: 311 to 519 Vac |
|
| Frequency Range | 50 or 60 Hz, ±5 Hz, auto detecting | |
| Input Current Distortion | <5% with IT loads (PFC power supplies) | |
| Input Power Factor | >.99 with IT loads (PFC power supplies) | |
| Inrush Current | Load dependent | |
| Input Requirements | Three-phase, four wire + ground | |
| Bypass Source | Same as input, (single feed) | |
| Generator Compatibility | Fast sync slew rate for optimum generator operation | |
| Output Characteristics | ||
| Rated Output Voltage | 208V model: Programmable
180 to 229 Vac, Ph to Ph (standard) 187 to 229Vac ph to jph (ITEC optimized) 400V model: 180 to 240 Vac, Ph to N |
|
| Output Configuration | Three-phase, four wire + ground | |
| Output Frequency (nominal) | 50 or 60 Hz auto-detection on startup | |
| Frequency Regulation | 0.1 Hz free running | |
| Load Power Factor Range |
Lagging: 0.7 Leading: 0.85 |
|
| Total
Output Voltage Distortion |
<3% with IT loads (PFC power supplies) <5% non-linear or non-PFC power supplies |
|
| Battery Characteristics | ||
| Battery Type | VRLA - AGM | |
| Battery Runtime (Internal) | 13.6
minutes at 50% load 4.7 minutes at 100% load |
|
| Battery String Voltage | 240 Vdc (Internal redundant strings in each module) | |
| Battery Test |
Automatic battery test standard (remote scheduling capable). Manual battery test from front display |
|
| Battery Recharge Profile |
ABM Technology. Advanced three-stage charging technique |
|
| Battery Cut-off Voltage |
Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min.
runtime |
|
| Battery Low Condition | Announced with alarm | |
| Battery Load Share | Yes: based on battery voltage during discharge. Load shifted to systems with strongest batteries to give longest runtime for battery condition | |
| Extended Battery Capability |
Yes, add up to four additional 3U battery enclosures >34 min at
100% load, >1 hour at 50% load) |
|
| Physical Characteristics | ||
| Dimensions (HxWxD) Installed Shipped EBM |
10.5 (6U) x 17.4 x 26.0 inches 266 x 438 x 660mm 27 x 39 x 46 inches 686 x 991 x 1168 mm 5.2 (3U) x 17.2 x 26 inches 132 x 437 x 660 mm |
|
| Note: Total Chassis Weight without batteries or electronics Total Chassis Weight with batteries or electronics |
100 lb. (46 kg) 307 lb. (140 kg) |
|
| Total UPS Weight without Batteries | 135 lb. (61 kg) | |
| Total UPS Weight with Batteries | 307 lb. (140 kg) | |
| EBM Weight | 170 lb. (77 kg) | |
| Communications and User Interface | ||
| Software Compatibility | UPS ships with Software
Suite CD containing LanSafe power management software and trial version of PowerVision |
|
| X-Slot® Bays | Two available for the cards listed below | |
| Optional X-Slot Communication Cards | Application | Powerware Card |
| WEB - TCP/IP | ConnectUPS-X Web/SNMP Card | |
| Modbus® RTU | Modbus Card | |
| IBM eServer™ (i5™, iSeries™, or AS/400®) |
Relay Interface Card | |
| N/O, N/C (dry contacts) |
Industrial Relay Card | |
| Parallel | Powerware Hot Sync CAN Bridge Card | |
| Remote Monitoring | Modem card | |
| Power Xpert® Gateway Series 2000 Card | ||
| Control panel LCD |
Two lines by 20 characters Four menu-driven interface buttons Four status at a glance LEDs |
|
| Multi Language |
Standard: English, Spanish, French, German, and Portuguese Available: Finnish, Norwegian, Swedish, Russian, Hungarian, Polish, Romanian, Czech, Danish, Greek, Turkish, Bulgarian, Korean, and Chinese |
|
| Configuration Changes |
User capable, firmware auto configures. Online firmware updates available for operational changes |
|
| Dry Contact Inputs | Two, user configurable | |
| Dry Contact Outputs | One, user configurable | |
| Service | ||
| Installation | User capable, located in the IT racks, operational factory service available | |
| Preventative Maintenance | User capable, optional factory service available | |
| Corrective Maintenance | User capable, optional factory service available | |
| Serviceability Features |
Hot-swappable batteries Hot-swappable electronics module Automated internal maintenance bypass Auto-configure firmware Flash firmware upgradeable |
|
| Certifications | ||
| Safety | 208V model: UL1778, cUL 400V model: CE |
|
| EMI |
208V model: FCC Part15 Class A 400V model: EN62040-2 Class A |
|
| Surge Protection | ANSI C62.41, Cat B-3 | |
| Hazardous materials (RoHS) | Complies per EU Directive 2002/95/EC Category 3 (4 of 5) | |
| Warranty | ||
| Standard | 12 months from install / 18 months from shipment | |
| Warranty Repair | Factory depot repair or replace | |
| Service Support Agreements2 | ||
| Depot | PowerTrust Express | |
| On-site 5x8 | PowerTrust Value | |
| On-site 7x24 | PowerTrust eight-, six- or two-hour response | |
| Options and Accessories | ||
| Detachable input cord | ||
| Detachable input/output cord assembly | ||
| Detachable paralleling cord assembly | ||
| Extended Battery Modules (EBM) | ||
| 3U output sub-distribution modules (RPM) | ||
| 0U to 3U rack power strips | ||
| 60 kW Powerware BladeUPS Parallel bar | ||
| Environmental Monitoring Probe (EMP) for temperature and humidity monitoring | ||
| X-Slot Communication Cards (see Communications and User Interface above) | ||
| Remote monitoring service by Eaton: eNotify; requires purchase of Web Card and Environmental Monitoring Probe | ||