| Powerware 9355 | |||||||
| Rating | 8kVA | 10kVA | 12kVA | 15kVA | 20kVA | 30kVA | |
| Capacity (VA/watts) | 8 / 7.2 | 10 / 9 | 12 / 10.8 | 15 / 13.5 | 20 / 18 | 30 / 27 | |
| Dimensions HxWxD (mm) UPS + BAT UPS + 2*BAT |
817x305x702 1214x305x702 |
817x305x702 1214x305x702 |
817x305x702 1214x305x702 |
817x305x702 1214x305x702 |
1684x484x762 |
1684x484x762 |
|
| Weight (kg) UPS + BAT UPS + 2*BAT |
155 kg 265 kg |
155 kg 265 kg |
160 kg 270 kg |
160 kg 270 kg |
200 kg 300-500 kg |
300 kg 400-500 kg |
|
| Input connection | Hardwired | ||||||
| Output connection | Hardwired | ||||||
| Typical runtime at +25 ºC. | UPS + BAT | 15 min | 10 min | 8 min | 5 min | 5 min | - min |
| UPS + 2BAT | 33 min | 25 min | 20 min | 15 min | 13 min | 7 min | |
| Operational | |||||||
| Nominal input voltage (Vac) | 220/380, 230/400, 240/415 Vac three phase | ||||||
| Input voltage range | +20%, -20% | ||||||
| Operating frequency | 50/60 Hz (45 to 65 Hz) | ||||||
| Input power factor | 0.99 | ||||||
| Input current distortion | 5% THD | ||||||
| Nominal output voltage | 220/380, 230/400, 240/415 Vac three phase | ||||||
| Output voltage regulation | ±2% static; ±5% dynamic at 100% load change, <1 ms response time |
||||||
| Overload capacity | 150%
for 5 sec / 125% for 1 min (online), 1000% for 5 msec (bypass) |
||||||
| Efficiency | 92% with rated non-linear load | ||||||
| User interface | |||||||
| LCD-display | Std. Graphical LDC with blue back light | ||||||
| LED | 4 LED | ||||||
| Standard communication ports |
1 x RS232 for local support, 2 x X-slot (empty); 1 x relay contacts, 2 x input contacts, 1 x emergency power off input |
||||||
| Optional | External
battery cabinets; Isolation transformer; X-slot: SNMP/web, Modbus/Jbus, Relay card; |
||||||
| Environmental | |||||||
| Operating Temperature | 0ºC to +40 ºC | ||||||
| Storage Temp | -15°C to +40°C | ||||||
| Altitude | < 1000 M | ||||||
| Audible Noise at 1 meter; | <50 dB | ||||||
| Certification | |||||||
| Quality | ISO 9001 | ||||||
| Markings | CE-marking | ||||||
| Safety | IEC 62040-1-1, IEC 60950 | ||||||
| EMC | EN 50091-2 Class A | ||||||