Input
Voltage Range  +10% to -15%
Frequency Range +/-5%
Surge Protection  Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2
Power Factor  0.95 Typical at full load with input filter
Output
Voltage Regulation Better than +/- 1%
Voltage THD  Less than 5% (100% nonlinear load); Less than 3% (100% linear load)
Transient Response  Less than 5% for 100% load, step full recovery within 1 cycle
Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1
Safety (pending)
UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed EN 50091-1
All Cabinets provide seismic mounting features, selectable DC ground fault detection capability
Environmental
Audible Noise  <75 dBA at 1 meter
Ambient Operating Temperature  0°C to 40°C
Ambient Storage Temperature  -20°C to 70°C
Altitude 5000 ft. (1500 m) at 40°C without derating
Relative Humidity  5-95% non-condensing
EMC Meet FCC Class A, EN 50091-2 (CISPR 22, Class A, Restricted Access)
Electrostatic Discharge Withstands 25kV without damage or disturbance to load
*Specifications subject to change without notice.

Go to top

Model Selection Guide

   9315-750  9315-750/625
  750 kVA/600 kW   625 kVA/500 kW
Input Voltage  volts  480  600  480 600
Output Voltage  volts  480  600  480 600
Input Voltage Range 
 Minimum  volts  408  510  408 510
 Maximum  volts  528  660  528  600
Input/Output Frequency  Hz 60 60  60  60
AC Input (with input filter)
 Nominal Amps  amps  913 730  761 609
 Maximum Amps  amps  1141 913  951 761
Bypass Input  
 Nominal Amps  amps  902  722  752  601
AC Input (without input filter)
 Nominal Amps  amps  902  722  752  601
 10 minutes max  amps  1128  902  940  752
DC Link 
 Nominal DC Voltage  volts  384 384  384  384
Float Voltage  volts  432 432  432  432
End of Discharge  volts  320 320  320  320
Nominal Amps  amps  1954 9554  1628  1628
Physical Attributes (w/o batt.) 
Single Module RT Configurations 
 Installed Weight  lbs  13,200 13,200  13,200  13,200
 Installed Width  inches  149"  149"  149"  149"
 Multimodule Configurations 
 Installed Weight  lbs  12,600  12,600  12,600  12,600
 Installed Width  inches  126 5/8"  126 5/8"  126 5/8"  126 5/8"
System Efficiencies 
 100% Load  %  94  94  94  94
 75% Load   %  94  94  94  94
 50% Load   %  93  93  93  93
Full Load Heat Dissipation 
 BTU/Hr. (x1000)   130.8 130.8   109.0  109.0
 KCal/Hr. (x1000)   33.0 33.0  27.5  27.5
Inverter Efficiency (Full Load)
   %  95  95  95  95