| Input | |
| Voltage Range | See table below |
| Frequency Range | (60 Hz) 57-64 Hz |
| Surge Protection | Meets ANSI C62.41, Category A & B EN 50091-2 and EN50082-2 |
| Power Factor | 0.95 Typical at full load with input filter |
| Output | |
| Voltage Regulation | Better than +/- 1% |
| Voltage THD | Less than 5% (100% nonlinear load); Less than 3% (100% linear load) |
| Transient Response | Less than 5% for 100% load, step full recovery within 1 cycle |
| Frequency Regulation | (Free Run) +/- 0.005 Hz |
| Frequency Sync Range | +/- 0.5 Hz |
| Frequency Slew Rate | 1 Hz/sec. |
| Load Crest Ratio | 3:1 |
| Power Factor | 0.9 (Optional) |
| Battery | |
| Battery Type | Sealed, valve regulated lead acid |
| Recharge time | 10-12x discharge to 95% capacity |
| Safety | UL 1778
Listed CUL CAN/CSA C22.2NO.107.1-M91 Listed All Cabinets provide seismic mounting features selectable DC ground fault detection capability |
| Environmental and safety | |
| Audible Noise | <72 dBA at 1 meter |
| Ambient Operating Temperature | 0°C to 40°C |
| Ambient Storage Temperature | -20°C to +70°C |
| Altitude | 5000 ft. (1500 m) without derating |
| Relative Humidity | 5-95% non-condensing |
| EMI Suppression | Meet FCC
Class A, Subpart J of Part 15 and EN 50091-2 (CIPR22,ClassA) |
| Electrostatic Discharge | Withstands 25kV without damage or disturbance to load |
* Specifications subject to change without notice.
Battery
Run Times (in
minutes)
| 50 Hz Applications | |||||
| Model Number | 9315-400 | ||||
| kVA | 300 | 300 | 400 | 400 | |
| kW | 240 | 270 | 320 | 360 | |
| Battery Type |
Number Parallel Strings |
||||
| J37 - UPS12-370 | 2 | 7 | 5 | - | - |
| C39 - HRL12390 | 2 | 7 | 5 | - | - |
| J47 - UPS12-475 | 2 | 8 | 6 | - | - |
| C50 - HRL12500 | 2 | 9 | 7 | - | - |
| J27 - UPS12-270 | 3 | 9 | 7 | - | - |
| C28 - HRL12280 | 3 | 9 | 7 | - | - |
| J31 - UPS12-310 | 3 | 11 | 9 | 6 | - |
| C33 - HRL12330 | 3 | 12 | 9 | 6 | - |
| J37 - UPS12-370 | 3 | 15 | 11 | 9 | 7 |
| C39 - HRL12390 | 3 | 16 | 12 | 10 | 7 |
| J47 - UPS12-475 | 3 | 19 | 15 | 11 | 8 |
| C50 - HRL12500 | 3 | 20 | 16 | 12 | 10 |
| J27 - UPS12-270 | 4 | 14 | 11 | 9 | 7 |
| C28 - HRL12280 | 4 | 14 | 12 | 10 | 7 |
| J31 - UPS12-310 | 4 | 18 | 14 | 11 | 9 |
| C33 - HRL12330 | 4 | 19 | 15 | 12 | 10 |
| J37 - UPS12-370 | 4 | 23 | 19 | 15 | 11 |
| C39 - HRL12390 | 4 | 24 | 20 | 15 | 12 |
| J47 - UPS12-475 | 4 | 31 | 26 | 19 | 15 |
| C50 - HRL12500 | 4 | 31 | 27 | 20 | 16 |
| Nominal DC Link Voltage | 420 | 420 | 420 | 420 | |