| Input | |
| Voltage Range | See table below |
| Frequency Range | (60Hz) 57-64 Hz (50Hz) 47-53 Hz |
| Surge Protection | Meets ANSI C62.41, Category A & B EN 50091-2 and EN50082-2 |
| Power Factor | 0.95 Typical at full load with input filter |
| Output | |
| Voltage Regulation | Better than +/- 1% |
| Voltage THD | Less than 5% (100% nonlinear load); Less than 3% (100% linear load) |
| Transient Response | Less than 5% for 100% load, step full recovery within 1 cycle (2.5 ms) |
| Frequency Regulation | (Free Run) +/- 0.005 Hz |
| Frequency Sync Range | +/- 0.5 Hz |
| Frequency Slew Rate | 1 Hz/sec. |
| Load Crest Ratio | 3:1 |
| Battery | |
| Battery Type | Sealed, maintenance-free lead acid |
| Recharge time | 10-12x discharge to 95% capacity |
| Safety | UL 1778
Listed CUL CAN/CSA C22.2NO.107.1-M91 Listed All Cabinets provide seismic mounting features selectable DC ground fault detection capability |
| Environmental and Safety | |
| Audible Noise | <65 dBA at 1 meter |
| Ambient Operating Temperature | 0C to 40C |
| Ambient Storage Temperature | -20C to +70C |
| Altitude | 5000 ft. (1500 m) without derating |
| Relative Humidity | 5-95% non-condensing |
| EMI Suppression | Meet FCC
Class A, Subpart J of Part 15 and EN 50091 (CIPR22,ClassA) |
| Electrostatic Discharge | Withstands 25 kV without damage or disturbance to load |
* Specifications subject to change without notice.
Battery
Run Times (in
minutes)
| 50 Hz Applications | |||||||
| Model Number | 9315-200 | 9315-250 | |||||
| kVA | 200 | 200 | 200 | 200 | 250 | 250 | |
| kW | 160 | 180 | 160 | 180 | 200 | 225 | |
| Battery Type |
Number Parallel Strings |
||||||
| J27 - UPS12-270 | 2 | 9 | 7 | 9 | 7 | 5 | - |
| C28 - HRL12280 | 2 | 9 | 7 | 9 | 7 | 5 | - |
| J31 - UPS12-310 | 2 | 11 | 9 | 11 | 9 | 7 | 6 |
| C33 - HRL12330 | 2 | 12 | 10 | 12 | 9 | 8 | 6 |
| J37 - UPS12-370 | 2 | 15 | 11 | 15 | 11 | 11 | 8 |
| C39 - HRL12390 | 2 | 16 | 13 | 16 | 13 | 11 | 9 |
| J47 - UPS12-475 | 2 | 19 | 15 | 19 | 15 | 13 | 9 |
| C50 - HRL12500 | 2 | 20 | 17 | 20 | 17 | 14 | 11 |
| J27 - UPS12-270 | 3 | 17 | 13 | 17 | 13 | 12 | 9 |
| C28 - HRL12280 | 3 | 18 | 14 | 18 | 13 | 13 | 10 |
| J31 - UPS12-310 | 3 | 21 | 18 | 21 | 18 | 15 | 12 |
| C33 - HRL12330 | 3 | 22 | 19 | 22 | 19 | 16 | 13 |
| J37 - UPS12-370 | 3 | 27 | 22 | 27 | 22 | 19 | 15 |
| C39 - HRL12390 | 3 | 27 | 23 | 27 | 23 | 20 | 17 |
| J47 - UPS12-475 | 3 | 37 | 29 | 37 | 29 | 26 | 21 |
| C50 - HRL12500 | 3 | 37 | 30 | 37 | 30 | 27 | 22 |
| J27 - UPS12-270 | 4 | 27 | 21 | 27 | 21 | 19 | 15 |
| C28 - HRL12280 | 4 | 27 | 22 | 27 | 21 | 20 | 16 |
| J31 - UPS12-310 | 4 | 32 | 27 | 32 | 27 | 24 | 19 |
| C33 - HRL12330 | 4 | 33 | 28 | 33 | 28 | 25 | 20 |
| J37 - UPS12-370 | 4 | 39 | 32 | 39 | 32 | 30 | 24 |
| C39 - HRL12390 | 4 | 39 | 33 | 39 | 33 | 30 | 25 |
| J47 - UPS12-475 | 4 | 54 | 46 | 54 | 46 | 41 | 32 |
| C50 - HRL12500 | 4 | 54 | 46 | 54 | 46 | 41 | 33 |
| Nominal DC Link Voltage | 420 | 420 | 420 | 420 | 420 | 420 | |