| Electrical Input | 700 - 3000 VA | 5000/6000 VA |
| Nominal Voltage | 120 Vac, 208 - 240 Vac | 208 - 240 Vac |
| Voltage Range | 120 V: 80-144 V (without using
batteries) 208/230 V: 160 - 288 V (without using batteries) |
123-208 V (without using batteries) |
| Input Power Factor | >.95, typical | >.96 in any mode |
| Frequency | 50/60 Hz, auto-sensing | |
| Frequency Range | 45 - 65 Hz | 50 Hz: 47-53 Hz 60 Hz: 57-63 Hz |
| Electrical Output | ||
| On Utility Voltage Regulation | ±3% of nominal | |
| On Battery Voltage Regulation | ±3% of nominal | |
| Efficiency | 89 - 92%, depending on load | >85% Online Mode; >90% High-efficiency Mode |
| Frequency Regulation | ±3 Hz online; ±1 Hz on battery | ±3 Hz online; ±1
Hz on battery; ±3 Hz High-Efficiency Mode |
| Load Crest Factor | 3 to 1 ratiod> | |
| Communications | ||
| Serial Port | RS-232 communications port standard; optional X-slot modules available |
RS-232 and USB communications port
standard; optional X-slot modules available |
| Communications Cable | 6-foot communications cable included | |
| Battery | ||
| Internal Battery type | 9 Ah, Sealed, lead-acid; maintenance free | 7 Ah, Sealed, lead-acid; maintenance free |
| EBM Battery Type | 9 Ah, Sealed, lead-acid; maintenance free | 9 Ah, Sealed, lead-acid; maintenance free |
| On Battery Runtime | See Battery Runtimes | |
| Battery Replacement | Hot-swappable internal and external batteries | |
| Recharge Time | <2 hrs. From complete discharge to 80% capacity at nominal line conditions | |
| Start-On-Battery | Allows start of UPS without utility input | |
| General | ||
| Topology | True online, double-conversion | |
| Diagnostics | Full system self-test on power up | |
| UPS Bypass | Automatic on overload or UPS failure | |
| Dimensions and Weights | See Model Selection Guide | |
| Environmental and Safety | ||
| Safety Markings | 120 V: UL, CSA and NOM 230 V: UL, CSA, VDE, CE, S, D, N, FI, B, NOM, R 208 V: UL, CSA |
UL, cUL, VDE, CE, NOM, NYCE, GS |
| EMC Markings | FCC Class B and VCCI Class II, 3000 FCC Class A | FCC-A, VCCI-A, BSMI-A, C-Tick, CE Compliance |
| Surge Suppression | IEEE/ANSI C62.41 Category B (formerly 587) | ANSI C62.41 Category B3, and EN61000-4-5 Level 3 Criteria B |
| Audible Noise | <45 dBA (on utility); <50 dBA (on battery) | |
| Ambient operating | 0°C to 40°C (32°F to 104°F); 0°C to 25°C (32°F to 77°F) | |
| Heat Dissipation | 2066 BTU/hr. Max | |
| Leakage Current | < .6mA Typical | |
| Storage Temperature | ||
| Relative Humidity | 0 to 90%, non-condensing | 5 to 90%, non-condensing |
| REPO Port | NEC Code 645-11 intent and UL requirements | |
| Network Transient Protector | In and out jack for models only or 10Base-T network cable; protection. UL497A tested | N/A |
Specifications are typical and subject to change without notice due to continuing product improvement programs.
| Model Number1 |
Power Rating (VA/Watt) |
Input Connection4 |
Output Receptacles |
Dimensions HxWxD (in / mm) |
Unit Wt. (lb/kg)6 |
| 120 Vac Models2 | |||||
| PW9125 700 |
700/490 | 5-15P | (6) 5-15R | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
34/15 |
| PW9125 1000 |
1000/700 | 5-15P | (6) 5-15R | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
34/15 |
| PW9125 1500 |
1500/1050 | 5-15P | (6) 5-15R | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
50/23 |
| PW9125 2000 |
2000/1400 | 5-20P | (6) 5-15R | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
50/23 |
|
PW9125 2000 20R |
2000/1400 | 5-20P |
(2) 5-15R, (4) 5-20R |
3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
50/23 |
| PW9125 2500U |
2500/1750 | L5-30P | (2)5-15R, (2)5-20R (1)L5-30R |
3.5 x 17.0 x 23.9 / 89 x 432 x 607 |
81.5/37 |
|
PW9125 3000U |
3000/2100 | L5-30P |
(2)5-15R, (2)5-20R (1) L5-30R |
3.5 x 17.0 x 23.9 / 89 x 432 x 607 |
81.5/37 |
| 208 Vac Models3 | |||||
| PW9125 2500G |
2500/1750 | Detachable L6-20P |
(4) IEC 320-C13 (1) IEC 320-C19 |
3.5 x 17.0 x 23.9 / 89 x 432 x 607 |
81.5/37 |
| PW9125 3000G |
3000/2100 | Detachable L6-20P |
(4) IEC 320-C13 (1) IEC 320-C19 |
3.5 x 17.0 x 23.9 / 89 x 432 x 607 |
81.5/37 |
| PW9125 2500G HW |
2500/1750 | Hardwired | Hardwired | 3.5 x 17.0 x 23.9 / 89 x 432 x 607 |
81.5/37 |
| PW9125 3000G HW |
3000/2100 | Hardwired | Hardwired | 3.5 x 17.0 x 23.9 / 89 x 432 x 607 |
81.5/37 |
| 230 Vac Models4 | |||||
| PW9125 1000i |
1000/700 | IEC 320-C14 | (6) IEC 320-C13 | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
34/15 |
| PW9125 1500i |
1500/1050 | IEC 320-C14 | (6) IEC 320-C13 | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
50/23 |
| PW9125 2000i |
2000/1400 | IEC 320-C14 | (6) IEC 320-C13 | 3.5 x 17.0 x 19.4 / 89 x 432 x 494 |
50/23 |
| PW9125 5000g HW |
5000/3500 | Hardwired | (Hardwired | 8.63 x 17.37 x 24.94 / 219 x 441 x 633 |
206/93.4 |
| PW9125 5000g |
5000/3500 | L6-30P | L6-30R | 8.63 x 17.37 x
24.94 / 219 x 441 x 633 |
206/93.4 |
| PW9125 6000g HW |
6000/4200 | Hardwired | Hardwired | 8.63 x 17.37 x 24.94 / 219 x 441 x 633 |
206/93.4 |
| PW9125 6000g |
6000/4200 | L6-30P | L6-30R | 8.63 x 17.37 x
24.94 / 219 x 441 x 633 |
206/93.4 |
| PW9125 6000g FC |
6000/4200 | L6-30P | L6-30R | 8.63 x 17.37 x 24.94 / 219 x 441 x 633 |
206/93.4 |
1 50/60 automatic frequency selection.
2 120 V models are 110 V, 120 V, 127 V user-selectable.
3 208 V models are 208 V, 220 V, 230 V, 240 V user-selectable.
4 230 V models are 208 V, 220 V, 230 V, 240 V user-selectable.
5 Add 8.5 lb. for shipping weight.
Optional POWERPASS Power Distribution Modules (PDMs)
| Model1 | Input Voltage (VAC) | Output Voltage (VAC) | Input Connection |
Output Receptacles |
Dimensions (H x W x D) |
Weight (lb) |
| 700 - 2000 VA Models | ||||||
| PPDM 700-1500 VA | 120 | 120 | 6-ft, L5-15P attached power cord |
(6) 5-15R, (1) L5-15R for Laser Printer Unprotected |
3.5 x 11.0 x 4.5 | 2.5 |
| PPDM 2000 VA | 120 | 120 | 6-ft, L5-20P attached power cord |
(6)5-15R | 3.5 x 11.0 x 4.5 | 2.5 |
| PPDM 700-2000 VA | 230 | 230 | IEC 320-C14 Input Connector |
(6) IEC 320-C13, (1) IEC 320-C13 for Laser Printer Unprotected |
3.5 x 11.0 x 4.5 | 2.5 |
| 2500/3000 VA Models | ||||||
| PDM2-LV-US-P1 | 120 | 120 | 6-ft, L5-30P attached power cord |
(6) 5-20R (1) L5-30R |
3.0 x 17.0 x 23.9 | 20 |
| PDM1-HV-US-P1 | 208-240 | 208-240 / 120 | 16A, IEC 320-C20 Input Connector Country-specific, detachable power cord |
(6) 5-20R (1) L14-30R |
3.0 x 17.0 x 23.9 | 50 |
| PDM2-HV-US-P1 | 208-240 | 208-240 | 16A, IEC 320-C20
Input Connector Country-specific, detachable power cord |
(1) L6-30R | 3.0 x 17.0 x 23.9 | 20 |
| PDM2-LV-US-HW | 120 | 120 | 30A Terminal block (3 terminals) |
30A Terminal block (3 terminals) |
3.0 x 17.0 x 23.9 | 20 |
| 5000/6000 VA Models | ||||||
| PPDM, L6-30 | 208-240 | 208-240/120 | L6-30P | (1) L6-30R (8) 5-15R |
5.25 x 17.37 x 24.75 | 106 |
| PPDM, L6-20 | 208-240 | 208-240/120 | L6-30P | (1) L6-20R (8) 5-15R |
5.25 x 17.37 x 24.75 | 106 |
| PPDM, L5-30 | 208-240 | 208-240/120 | L6-30P | (1) L5-30R (8) 5-15R |
5.25 x 17.37 x 24.75 | 106 |
| PPDM, L14-30 | 208-240 | 208-240/120 | L6-30P | (1) 14-30R (8) 5-15R |
5.25 x 17.37 x 24.75 | 106 |
| PPDM, HW | 208-240 | 208-240/120 | Hardwired | Hardwired | 5.25 x 17.37 x 24.75 | 106 |
| PPDM, EURO HW | 208-240 | 208-240/120 | Hardwired | Hardwired | 5.25 x 17.37 x 24.75 | 106 |
| PPDM, L6-30&L14-30 | 208-240 | 208-240/120 | L6-30P | (1) L6-30R (1) L14-30R (4) 5-15R |
5.25 x 17.37 x 24.75 | 106 |
| PPDM, L6-30 (2) | 208-240 | 208-240/120 | L6-30P | (2) L6-30R (4) 5-20R |
5.25 x 17.37 x 24.75 | 106 |
| PPDM, L6-20 (2) | 208-240 | 208-240/120 | L6-30P | (2) L6-20R (4) 5-20R |
5.25 x 17.37 x 24.75 | 106 |
1 5000/6000 VA PDM Black Chassis Option, change order number from -55XX to -65XX
Optional Extended Battery Modules (EBMs)
| Model Number1 |
Part Number | Dimensions (HxWxD) |
Weight (lb) |
| PW9125 24 EBM For 700/1000 VA models only |
05146502-6591 | 3.5 x 17.0 x 19.4 | 65 |
| PW9125 48 EBM For 1250, 1500, 2000 VA models only |
05146074-6591 | 3.5 x 17.0 x 19.4 | 65 |
| PW9125 72 EBM For 2500 & 3000 models only |
103002836-6591 | 3.5 x 17.0 x 23.9 | 93 |
| PW9125 240 EBM For 5000 & 6000 models only |
103003387-6591 | 5.25 x 17.0 x 24.75 | 169 |
| PW9125 48Vdc Extended Battery Cabinet | 124100014-002 | 17.2 x 24.6 x 28.3 | 665 |
1 Black Chassis Option, change order number from -5501 to -6501 (for 700 VA - 2000 VA & 5000/6000 VA models only)
Battery Run Times (in minutes)
| 700/1000 VA Models | |||
| Load | Standard Internal Batteries |
1 EBM | 2 EBMs |
| 200 VA/140 W | 37 | 271 | 546 |
| 400 VA/280 W | 19 | 142 | 278 |
| 700 VA/490 W | 9 | 72 | 156 |
| 850 VA/595 W | 6 | 59 | 124 |
| 1250 VA/875 W | 11 | 46 | 87 |
| 1000 VA/700 W | 5 | 48 | 104 |
| 1250-2000 VA Models | |||||
| Load | Standard Internal Batteries |
1 EBM | 2 EBMs | 3 EBMs | 4 EBMs |
| 400 VA/280 W | 46 | 177 | 331 | 501 | 682 |
| 700 VA/490 W | 25 | 96 | 180 | 272 | 370 |
| 850 VA/595 W | 21 | 76 | 142 | 214 | 292 |
| 1000 VA/700 W | 16 | 61 | 115 | 174 | 237 |
| 1250 VA/875 W | 11 | 46 | 87 | 131 | 179 |
| 1500 VA/1050 W | 8 | 37 | 70 | 106 | 144 |
| 1800 VA/1260 W | 6 | 30 | 57 | 85 | 116 |
| 2000 VA/1400 W | 5 | 26 | 49 | 74 | 100 |
| 2500-3000 VA Models | |||||
| Load | Standard Internal Batteries |
1 EBM | 2 EBMs | 3 EBMs | 4 EBMs |
| 1250 VA/875 W | 16 | 57 | 90 | 150 | 200 |
| 1500 VA/1050 W | 13 | 55 | 72 | 120 | 160 |
| 2500 VA/1750 W | 7 | 28 | 48 | 68 | 88 |
| 3000 VA/2100 W | 5 | 25 | 38 | 54 | 70 |
| 5000-6000 VA Models | |||||
| Load | Standard Internal Batteries |
1 EBM | 2 EBMs | 3 EBMs | 4 EBMs |
| 1000 VA/700 W | 64 | 179 | 308 | 448 | - |
| 2000 VA/1400 W | 38 | 108 | 186 | 271 | 362 |
| 3000 VA/2100 W | 34 | 70 | 122 | 178 | 237 |
| 4000 VA/2800 W | 19 | 49 | 86 | 125 | 168 |
| 5000 VA/3500 W | 13 | 37 | 65 | 96 | 128 |
| 6000 VA/4200 W | 10 | 30 | 52 | 76 | 102 |
| Part Number | Description |
| 05146726-5591 | PW9215 700 - 3000 VA Mounting Rail Kit, 2-post 2U |
| 05141562-0091 | PW9215 700 - 3000 VA Mounting Rail Kit, 4-post 2U |
| 103005156 | PW9125 - 3000 VA Mounting Rail Kit, 4-post |
| 103003226 | PW9125 5000/6000 VA Mounting Rail Kit, Beach Grey |
| 103003226-001 | PW9125 5000/6000 VA Mounting Rail Kit, Black |
| 103003227 | PW9125 5000/6000 VA Pedestal Kit, Beach Grey |
| 103003227-001 | PW9125 5000/6000 VA Pedestal Kit, Black |
| 05146871-5501 | PW9125 700 - 3000 VA Seismic Kit, Three Unit (For 3 UPSs or EBMs) |
| 05146875-5501 | PW9125 700 - 3000 VA Seismic Kit, Five Unit (For 5 UPSs or EBMs) |
| 103003229-5501 | PW9125 5000/6000 Seismic Kit 3-unit (1-UPS, 2 PPDM or Battery) Beach Grey |
| 103003229-6501 | PW9125 5000/6000 Seismic Kit 3-unit (1-UPS, 2 PPDM or Battery) Black |
| Model | Part Number |
| X-Slot ConnectUPS-X Web/SNMP/xHub Card | 116750221-001 |
| X-Slot ConnectUPS-M Card | 05146288-5501 |
| X-Slot Multi-Server Card | 05146447-5502 |
| X-Slot Relay Card (AS/400 compatible) | 1018460 |
| X-Slot Modbus Card | 103002510-5501 |
| Expansion Chassis (equipped with Modbus card) | 5147063 |