Eaton Logo, links to the Eaton homepage

Powerware 9120 UPS Technical Specs

Model Selection Guide
Optional EBMs
Battery Runtimes
Available Options
Electrical Input
Nominal Voltage 120 Vac and 230 Vac; Model Selection Guide for user-selectable voltages
Input Voltage Range 120V: 80 –144 Vac
230V: 120/140/160-276 Vactd>
Input Power Factor >.95%
Operating Frequency 50/60 Hz, Auto-sensing
Frequency Range 45 - 65 Hz
Input Protection Fuse or circuit breaker
Electrical Output
On Utility Voltage Regulation +/-2% of nominal
On Battery Voltage Regulation +/-3% of nominal
Nominal Output Voltage Same as selected input voltage
Output Voltage Waveform Sine Wave
Output Voltage Distortion <3%THD
Output protection Electronic overload sensing, and circuit breaker protection
Efficiency Online Mode:>86%;
Hi-Efficiency Mode:>90%
Battery
Internal Battery type Sealed, lead-acid; maintenance free
EBM Battery Type Sealed, lead-acid; maintenance free
On Battery Runtime See Battery Runtimes
Battery Replacement Hot-swappable internal and external batteries
Recharge Time <4 hours to 90%capacity
Start-On-Battery Allows start of UPS without utility input
Communications
User Interface LCD status screen
Audible Alarms UPS alarm conditions, including:
On-Battery, Low Battery, Overload, UPS Fault
Network transient Protector In and out jack for all models.
UL497A tested
REPO Port Meets NEC code 645-11 intent and UL requirements
Communications One RS232 Serial Port; One Communications Slot; One USB Port
Communications cable 6-foot communications cable included
Power Management Software  Powerware Software Suite CD
General
Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on Overload or UPS failure <4ms
Transfer Time to battery 0 ms
Dimensions and Weights See Model Selection Guide
Overload Capacity  125% for 10 minutes before transfer to bypass;
150% for 10 seconds before transfer to bypass
Environmental and Safety
Safety Certifications UL1778;cUL22.2 NO.107.1
EMI Compliance FCC Part 15, Class B (700-1500), Class A (2000-3000) 230 V, 
EN 50091-2 Class B (700-1500), Class A (2000-3000)
Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature -15°C to 50°C (5°F to 122°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Relative Humidity 0%to 95%non-condensing
Immunity EEE C62.41,
IEC 61000-4 -2, -3, -4, -5
Network Transient Protector UL497A
Audible Noise at 1 meter 700-1000 VA: <45dB;1500 VA <50dB; 2000-3000 <52dB
Altitude  3000m (10,000 ft) without deteriorating

Note: Due to continuing product improvement programs, specifications are subject to change without notice.

Go to top

Model Selection Guide

Model
Number
Power Out
(VA/Watt)
Input/
Output
Voltage (Vac)
Frequency
(Hz)2
Input
Connection3
Output
Receptacles4
Dimensions
(HxWxD)
in/mm
Weight
(lb/kg)
120 Vac Models1
PW9120 700 700/490 120 50/60 5-15P (4) 5-15R 9.6 x 6.2 x 16.2/
243 x 158 x 412
29/13.2
PW9120 1000 1000/700 120 50/60 5-15P (4) 5-15R,
(2) 5-20R
9.6 x 6.2 x 16.2/
243 x 158 x 412
35.5/16.1
PW9120 1500 1500/1050 120 50/60 5-15P (4) 5-15R,
(2) 5-20R
10.8 x 6.7 x 17.5/
275 x 170 x 444
46.5/21.1
PW9120 2000 2000/1400 120 50/60 5-20P (6) 5-20R 14.2 x 8.6 x 18.6/
361 x 217 x 472
82/37.2
PW9120 3000 3000/2100 120 50/60 L5-30P (4) 5-15R,
(2) 5-20R
(1) L5-30R
14.2 x 8.6 x 18.6/
361 x 271 x x 472
89/40.5
PW9120 3000h 3000/2100 120 50/60 Hardwired Hardwired 14.2 x 8.6 x 18.6/
361 x 271 x x 472
89/40.5
208 Vac Models
PW9120 3000B 3000/2100 208 50/60 L6-20P (2)L6-15R,
(1)L6-20R,
(1)L6-30R
14.2 x 8.6 x 18.6/
361 x 217 x 472
89/40.5
230 Vac Models5
PW9120 700i 700/490 230 50/60 IEC-C14 (4)IEC-C13 9.6 x 6.2 x 16.2/
243 x 158 x 412
28/12.6
PW9120 1000i 1000/700 230 50/60 IEC-C14 (4)IEC-C13 9.6 x 6.2 x 16.2/
243 x 158 x 412
34/15.3
PW9120 1500i 1500/1050 230 50/60 IEC-C14 (4)IEC-C13 10.8 x 6.7 x 17.5/
275 x 170 x 444
44/19.8
PW9120 2000i 2000/1400 230 50/60 IEC-C14 ((4)IEC-C13,
(1)IEC-C19
14.2 x 8.6 x 18.6/
361 x 217 x 472
81.6/37
PW9120 3000i 3000/2100 230 50/60 IEC-C20 (4)IEC-C13,
(1)IEC-C19
14.2 x 8.6 x 18.6/
361 x 217 x 472
85/38.5
Optional Extended Battery Modules (EBMs)
PW9120 BATT 700 - - - Standard
Connector
- 9.6 x 6.2 x 16.2/
243 x 158 x 412
31/14
PW9120 BATT 1000 - - - Standard
Connector
- 9.6 x 6.2 x 16.2/
243 x 158 x 412
44/20
PW9120 BATT 1500 - - - Standard
Connector
- 10.8 x 6.7 x 17.5/
275 x 170 x 444
57/26
PW9120 BATT 2000 - - - Standard
Connector
- 14.2 x 8.6 x 18.6/
361 x 217 x 472
110/50
PW9120 BATT 3000 - - - Standard
Connector
- 14.2 x 8.6 x 18.6/
361 x 217 x 472
110/50

1 Also user-selectable for 100, 110, and 127 Vac.
2 Automatic frequency selection.
3 120V models have 6-ft. attached line cord. 230 V models have 6-ft. detachable line cord.
4 Divided into 2 Load Segments (receptacle groups).
5 Also user-selectable for 220 and 240 Vac

Go to top

Battery Run Times (in minutes full load/half load)

VA Standard
Internal
Battery
1 EBM 2 EBMs 3 EBMs 4 EBMs 5 EBMs
700 7/18 34/70 64/140 - - -
1000 7/18 36/80 66/155 - - -
1500 7/18 29/67 56/130 - - -
2000 12/34 49/107 93/195 140/310 192/403 240/504
3000 6/15 30/70 57/128 87/191 120/264 148/325
Up to 2 EBMs can be connected to 700/1000/1500 VA models and up to 5 EBMs can be connected to 2000/3000 VA models.Run time chart provides typical information.Run times are approximate and may vary with equipment,configuration,battery age,temperature,etc.  

 

Available Options

Order Number Description
IPK-0329 ConnectUPS-BD SNMP/WEB Card
1014018 AS/400 Relay Card
E-mail this page Print this page
Copyright ©2008 Eaton Corporation.