Eaton Logo, links to the Eaton homepage

Powerware 5125 Rackmount UPS Technical Specs

Model Selection Guide
EBMs
Battery Runtimes
Available Options
Electrical Input  1000-2200 VA 2400-3000 VA 5000/6000 VA
Nominal Voltage 120, 208 and 230 Vac;
 See Model Selection Guide for user-selectable voltages
120, 208 and 230 Vac2;
See Model Selection Guide for user-selectable voltages
200/208, 220, 230 and 240 Vac2
See Model Selection Guide for user-selectable voltages
Input Voltage Ranges (for user-selectable voltages) Low voltage: 77-152 V; High voltage: 154-288 V 160-288
Operating Frequency 50/60 Hz, Auto-sensing
Frequency Range 46-54 hz for 50 hz; 56-64 hz for 60 hz
Electrical Output
On Utility Voltage Regulation -10% to +6% of nominal
On Battery Voltage Regulation  ±5% RMS
Voltage Wave Shape (on battery)  Sine Wave
Output Protection  Short circuit protection
Battery
Battery Type Sealed, lead-acid; maintenance free
Battery Run time  See Battery Run Times Table
Battery Replacement Hot-swappable internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery Allows start of UPS without utility input
General
Electrical Power Module Replcmnt no yes, hot-swap yes, hot-swap
Diagnostics full system self-test on power up
UPS Bypass No Bypass Internal Bypass
Transfer Time 4ms typical, 6ms max
Dimensions and Weights  See Model Selection Guide
Overload (normal operation) 110% overload, shutdown after 3 minutes.
 150% overload, shut down 10 cycles
100-102 % indefinite 110% overload for 30 seconds short circuit protected
Communications
User Interface Front Control Panel
Audible Alarms For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault
Network Transient Protector UL 497 A, in/out jacks RJ45 (high voltage models network protection) & RJ11 (low voltage models modem protection) No
Communication Ports  see Communications Slot native USB and serial port
Communication Slot  RS-232 single serial module (standard) options available, see options chart Web/SNMPxHub card factory installed; other options also available
Cable 6-foot communications cable included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
Environmental 
Safety Certifications UL; cUL; NOM; C-Tick; CE marking UL; cUL; NOM; C-Tick; CE marking
TUV/VDE, GS
EMC Compliance FCC Part 15, EN50091-2, Class A for 2.2 KVA and RM; Class B for 1000 and 1500VA tower models FCC Part 15 EN50091-2, Class A
Operating Temperature  0°C to 40°C (32°F to 104°F) 10°C to 40°C
Storage Temperature -15°C to 50°C (5°F to 122°F) -25°C to 55°C
Relative Humidity 0% to 95% non-condensing
Lightning & Surge Protection  ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating high-energy 6500 A peak
Audible Noise less than 40 dBA typical less than 45 dBA typical
 Altitude  3000m (10,000 ft) without derating
Note: Specifications are subject to change without notice due to continuing product improvement programs.

Go to top

Model Selection Guide

Model
Number1
Power 
Rating (VA/Watt)
Input/
Output Voltage
(Vac)2
Input Connection Output Receptacles4 Dimensions HxWxD (in/mm) Weight (lb/kg) UPC CODE
Two-in-One Form Factor Models5 (North America)
PW5125
1000 RM
1000/900 120 5-15P,
6 ft line cord
(6) 5-15R 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67 790341033033
PW5125
1500 RM
1440/1340 120 5-15P,
6 ft line cord
(6) 5-15R 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67 790341033064
PW5125
2400 RM
2400/2250   120 L5-30P,
(12' attached)
 (1) L5-30R,
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40 790341035310
PW5125
3000 RM 
2880/2700 120 L5-30P,
(12' attached) 
(1) L5-30R,
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40 790341035273
Two-in-One Form Factor Models5 (International)
PW5125
1000i RM 
1000/900  230 IEC-320-10A,
inlet3
(6) IEC-320-10A (C13) 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67 790341033040
PW5125
1500i RM
1500/1340  230 IEC-320-10A,
inlet3
(6) IEC-320-10A (C13) 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67 790341033071
PW5125
2400i RM
2400/2250  230 IEC-309 16A P,
(12' attached) 
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40 790341035327
PW5125
3000g RM
3000/2700 200-240 IEC-320-16A,
receptacle
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40 790341035297
PW5125
3000e RM
3000/2700  230 IEC-320-16A,
receptacle
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40 790341035921
PW5125
3000i RM
3000/2700  230 IEC-309 16A P,
(12' attached) 
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40 790341035280
Rackmount Models6
PW 5125 5000 RM 5000/4500 200/208, 220, 230, 240 L6-30P L6-30R on short cord, (2) L6-20 (4) C13 5.25 x 17.50 x 26.0/
133 x 445 x 661
161/73 790341043414
PW 5125 6000 RM HW 6000/5400 200-240 HW (terminal block) HW, (4)C19, (4)C13 5.25 x 17.50 x 26.0/
133 x 445 x 661
161/73 790341043582
PW 5125 6000i RM 6000/5400 220, 230, 240 IEC309-32A IEC309-32A on short cord, (4)C19, (4)C13 5.25 x 17.50 x 26.0/
133 x 445 x 661
161/73 790341043421
1. 50/60 automatic frequency selection.
2. 120 V models are 110 V, 120 V, 127 V user-selectable. 230 V models are 220 V, 230 V, 240 V user-selectable. 208 V models are 208 V, 220 V, 230 V, 240 V user-selectable.
3. Includes (2) each IEC interconnect cables.
4. 1000-1500 VA models are divided into (2) Load Segments (receptacle groups). 2200-3000 VA models are divided into (3) Load Segments (receptacle groups). 5000/6000VA models are divided into (2) Load Segments.
5. Unit fits into standard 19-inch racks. Mounting kits are sold separately.
6. 5000/6000 VA models ship with both black and beige front panel bezels; models include rail kits and mounting hardware; factory installed ConnectUPS Web/SNMP/xHub card available by inserting -5507 for -5501.

Go to top

Optional Extended Battery Modules (EBMs)

MODEL
UPC CODE
DIMENSIONS
HxWxD (IN/MM)
WEIGHT
(LBS/KG)
For use with PW 5125 48 V EBM RM 1000/1500 VA RM models only 790341033101 3.5 x 17.0 x 19.4/
89 x 432 x 494
65.0/29.5
For use with PW 5125 120 RM 2400/3000 VA RM models only 790341035303 3.5 x 19.0 x 24.5/
89 x 483 x 622
121.0/54.9
For use with PW 5125 240 EBM (beach grey) 5000/6000 VA RM models only 790341041007 5.25 x 17.50 x 24.75/
133 x 445 x 629
169/76
For use with PW 5125 240 EBM (black) 5000/6000 VA RM models only 790341041014 5.25 x 17.50 x 24.75/
133 x 445 x 629
169/76

Go to top

Powerware 5125 Battery Run Time Chart (in minutes full load/half load)*

VA Standard Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
Two-in-one (rackmount and tower) models
1000 7/19 33/68 58/120 82/166 105/214
1500 5/13 23/57 49/161 73/172 96/205
2400 7/19 35/73 60/124 85/177 110/229
3000 5/15 25/61 49/103 69/146 90/190
Rackmount models
5000 7/19 24/61 46/106 67/156 89/210
6000 5/15 19/49 36/85 53/125 71/168

*Up to 4 EBMs can be connected to 1000-3000 VA models. EBM run times include internal batteries.
Run time chart provides typical information. Battery run times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

 Go to top

Available Options

Order Number Description
05141562-0091 4-post rackmount kit (1000-3000 VA rackmount models) fits 19-inch racks
05146726-5591 2-post rackmount kit (1000-3000 VA rackmount models) fits 19-inch racks
05146447-5502 Multi-Server Card
103005868-5591 Powerware Power Xpert Gateway Series 2000 Card
1018460 Relay Card
116750221-001 ConnectUPS Web/SNMP card
103002510-5501 Modbus Card
116750224-001 Environmental Monitoring Probe (EMP)
05146519-001  Powerpass Distribution Module (1000/1500 rackmount models only) 
05146401-5501 Power Distribution Unit 250 VA 0U form factor. Side cabinet mount (5000/6000 VA)
E-mail this page Print this page
Copyright ©2008 Eaton Corporation.