Powerware 9315 UPS Technical Specs

Rating (kVA) 300 kVA 400 kVA 625 kVA
Part number 9315-300 9315-400 9315-625
Capacity (kVA/KW) 300/270 400/360 625/562
Dimensions 6 pulse WxHxD mm single:
1880x1867x800 
 single:
1880x1867x800 
single/parallel:
3785x3226x2083/2083x991x991 
Weight  (kg) 2767 2767 5986/5714
Input connection Dual Input, hardwired Dual Input, hardwired Dual Input, hardwired
Output connection Hardwired Hardwired Hardwired
Typical runtime (full load) 10-30min 10-30min 10-30min
Operational
Nominal Input voltage (VAC) 220/380, 230/400, 240/415 VAC three-phase
Input voltage range 340 to 440 VAC
Operating frequency 50/60 Hz (47–63 Hz)
Input Power factor 0,95 with input filter option
Input current distortion 7% THD with input filter option
Nominal Output voltage 220/380, 230/400, 240/415 VAC three-phase
Output voltage regulation ±1% static; 
±5% dynamic at 100% load change
Overload capacity 101–125% for 10 min (on-line);
126–150% for 30 sec (on-line);
300% phase to neutral without bypass
1000% for  10 cycles (bypass)
Efficiency  92-94% (online); depending on model
User interface
LCD-display Status, measurements of performance, alarms and event log
LED UPS on, on battery, on bypass, notice, alarm
Standard communication ports 1x RS232 for local support; 1 x XSlot
2 relay contacts: programmable
6 programmable inputs: generator on, go to UPS, go to bypass, environment alarm;
1 emergency power off input
Optional External battery cabinets and racks;
remote monitor panel; relay interface module; maintenance bypass module; system bypass module; parallel capacity/redundancy systems
Environmental
Operating temperature 0°C - +40°C, 25°C recommended
Storage temperature --25°C – +60°C
Altitude < 1500 m
Audible noise at 1 meter 67-75 dBA (According to ISO 7779); depending on model
Certification
Markings CE
Safety EN 50091-1, UL1778 listed
EMC EN 50091-2 and FCC Class A