Eaton Logo, links to the Eaton homepage

Especificações Técnicas do UPS Powerware 9315 - 400 - 500 kVA

Model Selection Guide
Battery Runtimes 50Hz
Battery Runtimes 60Hz
200-300kVA Specs
Input
Voltage Range See table below
Frequency Range (60Hz) 57-64HZ
Surge Protection Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
Power Factor 0.95 Typical at full load with input filter
Output
Voltage Regulation Better than +/- 1%
Voltage THD Less than 5% (100% nonlinear load);
Less than 3% (100% linear load)
Transient Response Less than 5% for 100% load, step full recovery within 1 cycle
Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1
Power Factor 0.9 (Optional)
Battery
Battery Type Sealed, valve regulated lead acid
Recharge time 10-12x discharge to 95% capacity
Safety UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features selectable DC ground fault detection capability
Environmental and safety
Audible Noise <72 dBA at 1 meter
Ambient Operating Temperature 0C to 40C
Ambient Storage Temperature -20C to +70C
Altitude 5000 ft. (1500 m) without derating
Relative Humidity 5-95% non-condensing
EMI Suppression Meet FCC Class A, Subpart J of Part 15 and
EN 50091-2 (CIPR22,ClassA)
Electrostatic Discharge Withstands 25kV without damage or disturbance to load
* Specifications subject to change without notice. 

Go to top

Model Selection Guide

  9315-400 9315-400/300 9315-500  9315-500/400
 400kVA/320kW  300kVA/240kW  500kVA/400kW   400kVA/320kW
Input  Range
Input Voltage  volts  400 400  480  480 480 208
Output Voltage
Output Voltage  volts  400  400  480  480 208 208
Input Voltage Range
 Minimum  volts  340  340  408  408 408  177
 Maximum  volts  440  440  528  528  528  229
Input /Output Frequency  Hz 50/60 50/60 60  60  60  60
AC Input (with input filter)
 Nominal Amps  amps  508  381  556  445 445 1025
 Maximum Amps  amps  635  476  640  560 560 1280
AC Input (without input filter)
 Nominal Amps  amps  598  448  654  523 523 N/A
 Maximum Amps  amps  747  560  800 640  640 N/A
Bypass Input
 Nominal Amps  amps  577  433  600  480 480 1280
AC Output
 Nominal Amps  amps  577  433  600  480 1110 1110
 10 Minutes Max.  amps  721  541  750  600 1388  1388
DC Link
 Nominal DC Voltage  volts  420  420   480  480  480  480
 Float Voltage  volts  473  473  540  540  540  540
 End of Discharge  volts  351  351  401  401  401  401
 Maximum Amps  amps  914  686  1000  800  800  800
Physical Attributes (with-out battery)
 Installed Weight  lbs  6100  6100  6100  6100  10,100  14,100
 Installed Width  inches  74  74  74  74  123  172
System efficiencies
 100% Load  %  92  92  92  92  91  90
 75% Load   %  92  92  92  92  91  90
 50% Load   %  91  91  91  91  90  89
Full Load heat Dissipation
 BTU/Hr. (x1000)   95.6  71.7  95.6   107.3  107.3 119.0
 KCal/Hr. (x1000)   24.1 18.1  30.2  24.1  27.1 30.0
Inverter Efficiency (full load)
-   %  92.5  92.5  92.5  92.5  92.5  92.5

Go to top

Battery Run Times (in minutes)

50 Hz Applications
  Installed 9315-400
Battery
Type
Qty Cabinet
Series
Weight
(lbs.)
Width1
(inches)
300kVA
240kW
400kVA
320kW
J14 1 685 1,785 27 N/A N/A
J17 1 685 2,250 27 N/A N/A
H20 1       N/A N/A
J27 1 1085 2,865 43 N/A N/A
H30 1       N/A N/A
J31 1 1085 3,165 43 N/A N/A
J37 1 1085 3,395 43 N/A N/A
H40 1       N/A N/A
J47 1 1085 4,300 43 N/A N/A
H50 1       N/A N/A
J14 2 685 3,570 54 N/A N/A
J17 2 685 4,500 54 N/A N/A
H20 2       N/A N/A
J27 2 1085 5,730 86 N/A N/A
H30 2       N/A N/A
J31 2 1085 6,330 86 N/A N/A
J37 2 1085 6,790 86 7 N/A
H40 2       7 N/A
J47 2 1085 9600 86 8 N/A
H50 2       11 6
J27 3 1085 8,595 129 9 N/A
H30 3       9 N/A
J31 3 1085 9,495 129 11 6
J37 3 1085 10,185 129 15 9
H40 3       14 9
J47 3 1085 12,900 129 19 11
H50 3       21 14
J27 4 1085 11,460 172 14 9
H30 4       14 9
J31 4 1085 12,660 172 18 11
J37 4 1085 13,580 172 23 15
H40 4       22 14
J47 4 1085 17,200 172 31 19
H50 4       32 21
Nominal DC Link Voltage
          420 420
Number Of Cells per Cabinet
          210 210
1 All battery cabinets are 73.5 inches high and 31.5 inches deep. 

Go to top

60 Hz Applications
  Installed 9315-500
Battery
Type
Qty Cabinet
Series
Weight
(lbs.)
Width1
(inches)
400kVA
320kW
500kVA
400kW
J102 1 1085 2,545 43 N/A N/A
J14 1 685 1,915 27 N/A N/A
J17 1 685 2,450 27 N/A N/A
H20 1       N/A N/A
J27 1 1085 3,150 43 N/A N/A
H30 1       N/A N/A
J31 1 1085 3,495 43 N/A N/A
J37 1 1085 3,765 43 N/A N/A
H40 1       N/A N/A
J47 1 1085 4,800 43 N/A N/A
H50 1       N/A N/A
J14 2 685 3,830 54 N/A N/A
J17 2 685 4,900 54 N/A N/A
H20 2       N/A N/A
J27 2 1085 6,330 86 N/A N/A
H30 2       N/A N/A
J31 2 1085 6,990 186 N/A N/A
J37 2 1085 7,530 86 N/A N/A
H40 2       5 N/A
J47 2 1085 9,600 86 5 N/A
H50 2 1085 9,600 86 8 5
J27 3 1085 9,450 129 6 N/A
H30 3       7 N/A
J31 3 1085 10,485 129 8 5
J37 3 1085 11,295 129 12 7
H40 3       11 7
J47 3 1085 14,400 129 15 9
H50 3       17 12
J27 4 1085 12,600 172 11 7
H30 4       11 8
J31 4 1085 13,980 172 14 9
J37 4 1085 15,060 172 18 13
H40 4       17 13
J47 4 1085 19,200 172 25 17
H50 4       27 19
Nominal DC Link Voltage
          480 480
Number Of Cells per Cabinet
          240 240

Go to top

E-mail this page Print this page