Eaton Logo, links to the Eaton homepage

Especificações Técnicas do Powerware 9125 (Internacional)

External Battery Cabinets
Battery Runtimes
Powerware 9125
Rating  1000 VA 1500 VA 2000 VA 3000 VA 5000 VA 6000 VA
Part number  05146011-6591  05146006-6591  103006571-6591 103002723-6591 103003623-6591 103003625-6591
Capacity (VA/watts)  1000/700 1500/1050 2000/1400 3000/2100 5000/3500 6000/4200
Dimensions WxDxH (mm)  432*490*89  432*490*89  432*490*89  432*610*89  440*635*220  440*635*220
Weight (kg)  15 23 23 37 93 93
Input connection  IEC320/10A   IEC320/16A Hardwired
Output connection  6*IEC320 10A I IEC 16A
4 IEC 10A
Hardwired
Typical runtime  Full load 5 min 8 min  5 min 5 min 13 min 10 min
Half load 15 min  25 min 15 min  15 min  35 min  30 min
Operational
Nominal input voltage (Vac)  220/230/240 Vac 
Input voltage range  160-288 VAC(1000-3000 VA); 120-288VAC (6000 VA)
Operating frequency  50/60 Hz auto sensing 
Input power factor  >0,95 
Nominal output voltage   208/220/230/240 VAC 
Output voltage regulation +/-3% online; +/-3% on battery mode 
Overload capacity  Up to 110 % for 2 minute, 111-150% for 30 sec 
Efficiency >85% (1000-3000 VA); 90% (6000 VA)
>90% (700 VA); >93% 1000-3000 VA; >95% 5000-6000 VA (High efficiency mode)
User interface
LED  3 LEDs indigating UPS status
5 Alarm/Bar Graph indicators 
Standard communication ports   RS232 as standard (1000-3000 VA) ; RS232 and USB on 6000 VA 
Optional  SNMP, Multiserver card, relay card , Modbus card
Environmental
 Operating Temperature 0°C - +40°C
 Storage Temp Recommended 0°C - +25°C
 Altitude < 3000 M
 Audible Noise  < 45 dB normal mode
<50 dB battery mode
Certification
Markings  CE & UL 1778 (1000-2000 VA)
CE (3000 VA & 6000 VA) 
Safety  EN 50091-1 
EMC  EN 50091-2 
EN6100-3-2 (1000-3000VA)

Go to top

External Battery cabinets

Model
Number
Part Number Dimensions
(HxWxD)
Weight
PW9125 24 EBM 
1000 VA model
05146502-6591 432*490*89  30 kg
PW9125 48 EBM 
1500/2000 VA model
05146074-6591 432*490*89  30 kg
PW9125 72 EBM 
3000 model
103002836-5591 432*610*89  43 kg
PW9125 240 EBM 
6000 model
103003387-5591 440*629*133 77 kg

Go to top

Battery Run Times (in minutes)

1000 VA Models
Load Standard
Internal
Batteries
1 EBM 2 EBMs
500VA/350W 14 125 235
1000VA/700W 5 48 104
1500-2000 VA Models
Load Standard
Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
500VA/350W 35 150 300 450 600
1000VA/700W 16 61 115 174 237
1500VA/1050W 8 37 70 106 144
2000VA/1400W 5 26 49 74 100
3000 VA Model
Load Standard
Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
1000VA/700W 21 80 160 250 340
1500VA/1050W 13 55 72 120 160
2000VA/1400W 9 35 70 90 120
3000VA/2100W 5 25 38 54 70
5000-6000 VA Models
Load Standard
Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
2000VA/1400W 36 105 180 270 360
3000VA/2100W 24 70 120 175 237
4000VA/2800W 18 48 85 125 165
5000VA/3500W 13 37 65 96 128
6000VA/4200W 10 30 52 76 102