| Powerware 9120 | |||||||
| Rating | 700VA | 1000VA | 1500VA | 2000va | 3000VA | 5000VA | 6000VA |
| Part number | 05147361 -5501 |
05147362 -5501 |
05147363 -5501 |
05147364 -5501 |
05147365 -5501 |
1018289 | 1018290 |
| Capacity (VA/watts) | 700/ 490 |
1000/ 700 |
1500/ 1050 |
2000/ 1400 |
3000/ 2100 |
5000/ 3500 |
6000/ 4200 |
| Dimensions WxDxH (mm) | 155x410x240 | 170x445x275 | 215x470x365 | 280x580x570 | |||
| Weight (kg) | 13 | 15 | 20 | 37 | 38 | 91 | |
| Input connection |
IEC320/10A | IEC320/16A | Hardwired | ||||
| Output connection | 4xIEC320/10A | 1xIEC320/16A 4xIEC320/10A |
Hardwired | ||||
| Typical runtime Full load |
8 min | 8 min | 7 min | 14 min | 8 min | 10 min | 8 min |
| Typical runtime Half load |
20 min | 21 min | 20 min | 30 min | 20 min | 22 min | 20 min |
| Operational | |||||||
| Nominal input voltage (Vac) | 220/230/240 Vac | ||||||
| Input voltage range |
120/140/160-276 Vac(700-3000VA) | 120/140/184-276 Vac (5000-6000VA) | |||||
| Operating frequency | 50/60 Hz auto sensing (+/-3 Hz, adjustable) | ||||||
| Input power factor | >0,97 (700-3000VA) | >0,99 (5000-6000VA) | |||||
| Nominal output voltage |
208/220/230/240 VAC | ||||||
| Output voltage regulation |
+/-2% online; +/-3% on battery mode | ||||||
| Overload capacity | Up to 125 % for 1 minute, 125-150% for 10 sec | ||||||
| Efficiency | >86%
700VA; >88% 1000-3000VA ; >90% 5000-6000VA (Online mode) >90% 700VA; >93% 1000-3000VA ; >95% 5000-6000VA (High efficiency mode) |
||||||
| User interface | |||||||
| LCD display | LCD display showing both UPS meters and UPS settings | ||||||
| LED | Four LEDs; UPS On, UPS on Battery, UPS on bypass, Alarm | ||||||
| Standard communication ports | RS232 and USB as standard on all models | ||||||
| Optional | Connectivity slot for SNMP/WEB card and relay card | ||||||
| Environmental | |||||||
| Operating Temperature | 0°C to +40°C | ||||||
| Storage Temp | -15°C to +40°C | ||||||
| Altitude | < 3000 M | ||||||
| Audible Noise | <
45 dB (700-1500 \VA) |
<50 dB (2000-3000VA) |
<55 dB (5000-6000VA) |
||||
| Certification | |||||||
| Markings | CE/GS/UL
(700-2000VA) CE/GS (3000VA-6000VA) |
||||||
| Safety | EN 50091-1-1 & UL 1778
(700-2000VA) EN50091-1-1 (3000-6000VA) |
||||||
| EMC | EN
50091-2, EN6100-3-2 (700-3000VA) EN50091-2 (5000-6000VA) |
||||||
| Model | Dimensions | Weight |
|---|---|---|
| BAT 700 | 155 x 410 x 240 mm | 15 kg |
| BAT 1000 | 155 x 410 x 240 mm | 20 kg |
| BAT 1500 | 170 x 445 x 275 mm | 25 kg |
| BAT 2000/3000 | 215 x 470 x 365 mm | 50 kg |
| BAT 5000/6000 | 280 x 580 x 570 mm | 125 kg |