| UPS Rating (0.9 power factor) | ||||
| kVA | 40 | 80 | 120 | 160 |
| kW | 36 | 72 | 108 | 144 |
| General Characteristics | ||||
| Efficiency | 94% | |||
| Parallel Capability |
4x modules w/o tie cabinet; 8x with tie cabinet |
|||
| Audible Noise | <65dBA @ 1 meter | |||
| Altitude (max) | 2000m at 40º C | |||
| Input Characteristics | ||||
| Voltage | 208, 480, 600¹ | |||
| Voltage Range | +10% / -15% | |||
| Rated Frequency | 45-65 Hz | |||
| Power Factor | 0.99 (min) | |||
| Input Current Distortion | <4.5% (no input filter required) | |||
| Inrush | 6 times rated input current | |||
| Soft Start Capability | Yes | |||
| Internal Backfeed Protection | Yes | |||
| Output Characteristics | ||||
| Voltage | 208² , 480² , 600³ | |||
| Regulation | + / -1% | |||
| Inverter | PWM with IGBT Switching | |||
| Voltage THD |
< 1.5% (100% linear load); < 5% (non-linear load) |
|||
| Load Power Factor Range | 0.9 lagging to 0.9 leading | |||
| Battery | ||||
| Battery types | VRLA, AGM, Gel, Wet | |||
| Battery voltage | 384 - 480, variable | |||
| Temperature Compensation | Yes | |||
| Charging method | ABM technology | |||
| Dimensions | ||||
| Size (w x d x h) 40-80 kVA Modules |
18.9" x 31.6" x 73.7" | |||
| Weight (lbs) 40-80 kVA Modules |
600 | |||
| Size (w x d x h) 120-160 kVA Modules |
35.6" x 31.6" x 73.7" | |||
| Weight (lbs) 120-160 kVA Modules |
950 | |||
| User Benefits | ||||
| Control Panel (LCD) | 8 lines x 40 characters | |||
| Battery Start-up | Standard | |||
| Frequency Conversion | Standard | |||
| Remote Display Panel | Optional | |||
| Multi-language | Standard | |||
| Building Alarm Inputs | 2 (galvanic isolated) | |||
| Service | ||||
| Internal Input Breaker | Standard | |||
| Back/Side Against Wall Installation | Standard | |||
| Accessories | ||||
| System Parallel Cabinet | Optional | |||
| External Maintenance Bypass |
Optional | |||
| Integrated Distribution Cabinet | Optional | |||
| Isolation Transformer | Optional | |||
| Certification | ||||
| Safety | UL1778, CUL | |||
| EMC | FCC Class A | |||
| Surge | ANSI C62, 41 Cat. A&B | |||
| Remote Monitoring | ||||
| Monthly report via RJ45 LAN/Ethernet connection | Standard | |||
| Communications | ||||
| Software Compatibility | PowerVision, LanSafe, FORESEER | |||
| Communication Cards | Two X-Slots standard.
Maximum of four X-slots with
the Mini-CSB option. The following connectivity card
options can be installed at any time: -ConnectUPS Web/SNMP/xHub Card -Modbus Card -Relay Interface Card (Use for AS400 ’s) -Industrial Relay Card (5A@120V) -Parallel Card provides CAN communications, isolated RS-484 port -Environmental Monitoring Probe (EMP)* |
|||
| Remote Inputs/Outputs | Two building alarms inputs and one summary alarm contact (5A@120V)standard | |||
| Four more building alarm inputs available with the Mini-CSB option | ||||
| Remote Monitor Panel | Eight backlit status indicator lamps plus an audible horn** | |||