Eaton Logo, links to the Eaton homepage

Especificações Técnicas do Powerware 9120 (América do Norte)

Guia de Seleção de Modelos
Optional EBMs
Battery Runtimes
Available Options
Electrical Input
Nominal Voltage 120 Vac and 230 Vac; Model Selection Guide for user-selectable voltages
Input Voltage Range 120V: 80 –144 Vac
230V: 120/140/160-276 Vactd>
Input Power Factor >.95%
Operating Frequency 50/60 Hz, Auto-sensing
Frequency Range 45 - 65 Hz
Input Protection Fuse or circuit breaker
Electrical Output
On Utility Voltage Regulation +/-2% of nominal
On Battery Voltage Regulation +/-3% of nominal
Nominal Output Voltage Same as selected input voltage
Output Voltage Waveform Sine Wave
Output Voltage Distortion <3%THD
Output protection Electronic overload sensing, and circuit breaker protection
Efficiency Online Mode:>86%;
Hi-Efficiency Mode:>90%
Battery
Internal Battery type Sealed, lead-acid; maintenance free
EBM Battery Type Sealed, lead-acid; maintenance free
On Battery Runtime See Battery Runtimes
Battery Replacement Hot-swappable internal and external batteries
Recharge Time <4 hours to 90%capacity
Start-On-Battery Allows start of UPS without utility input
Communications
User Interface LCD status screen
Audible Alarms UPS alarm conditions, including:
On-Battery, Low Battery, Overload, UPS Fault
Network transient Protector In and out jack for all models.
UL497A tested
REPO Port Meets NEC code 645-11 intent and UL requirements
Communications One RS232 Serial Port; One Communications Slot; One USB Port
Communications cable 6-foot communications cable included
Power Management Software  Powerware Software Suite CD
General
Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on Overload or UPS failure <4ms
Transfer Time to battery 0 ms
Dimensions and Weights See Model Selection Guide
Overload Capacity  125% for 10 minutes before transfer to bypass;
150% for 10 seconds before transfer to bypass
Environmental and Safety
Safety Certifications UL1778;cUL22.2 NO.107.1
EMI Compliance FCC Part 15, Class B (700-1500), Class A (2000-3000) 230 V, 
EN 50091-2 Class B (700-1500), Class A (2000-3000)
Operating Temperature 0 to 40 C (32 to 104 F)
Storage Temperature -15 to 50 C (5 to 122 F)
Storage Temperature 0o to 25o C (32o to 77o F)
Relative Humidity 0%to 95%non-condensing
Immunity EEE C62.41,
IEC 61000-4 -2, -3, -4, -5
Network Transient Protector UL497A
Audible Noise at 1 meter 700-1000 VA: <45dB;1500 VA <50dB; 2000-3000 <52dB
Altitude  3000m (10,000 ft) without deteriorating
Note: Due to continuing product improvement programs, specifications are subject to change without notice.

Go to top

Model Selection Guide

Model
Number
Power Out
(VA/Watt)
Input/
Output
Voltage (Vac)
Frequency
(Hz)2
Input
Connection3
Output
Receptacles4
Dimensions
(HxWxD)
in/mm
Weight
(lb/kg)
120 Vac Models1
PW9120 700

700/490

120

50/60

5-15P

(4) 5-15R

9.6 x 6.2 x 16.2/
243 x 158 x 412

29/13.2

PW9120 1000

1000/700

120

50/60

5-15P

(4) 5-15R,
(2) 5-20R

9.6 x 6.2 x 16.2/
243 x 158 x 412

35.5/16.1

PW9120 1500

1500/1050

120

50/60

5-15P

(4) 5-15R,
(2) 5-20R

10.8 x 6.7 x 17.5/
275 x 170 x 444

46.5/21.1

PW9120 2000

2000/1400

120

50/60

5-20P

(6) 5-20R

14.2 x 8.6 x 18.6/
361 x 217 x 472

82/37.2

PW9120 3000

3000/2100

120

50/60

L5-30P

(4) 5-15R,
(2) 5-20R
(1) L5-30R

14.2 x 8.6 x 18.6/
361 x 271 x x 472

89/40.5

PW9120 3000h

3000/2100

120

50/60

Hardwired

Hardwired

14.2 x 8.6 x 18.6/
361 x 271 x x 472

89/40.5

208 Vac Models

PW9120 3000

3000/2100

208

50/60

L6-20P

(2)L6-15R,
(1)L6-20R,
(1)L6-30R

14.2 x 8.6 x 18.6/
361 x 217 x 472

89/40.5

230 Vac Models5
PW9120 700i

700/490

230

50/60

IEC-C14

(4)IEC-C13

9.6 x 6.2 x 16.2/
243 x 158 x 412

28/12.6

PW9120 1000i

1000/700

230

50/60

IEC-C14

(4)IEC-C13

9.6 x 6.2 x 16.2/
243 x 158 x 412

34/15.3

PW9120 1500i

1500/1050

230

50/60

IEC-C14

(4)IEC-C13

10.8 x 6.7 x 17.5/
275 x 170 x 444

44/19.8

PW9120 2000i

2000/1400

230

50/60

IEC-C14

((4)IEC-C13,
(1)IEC-C19

14.2 x 8.6 x 18.6/
361 x 217 x 472

81.6/37

PW9120 3000i

3000/2100

230

50/60

IEC-C20

(4)IEC-C13,
(1)IEC-C19

14.2 x 8.6 x 18.6/
361 x 217 x 472

85/38.5

Optional Extended Battery Modules (EBMs)
PW9120 BATT 700

-

-

-

Standard
Connector

-

9.6 x 6.2 x 16.2/
243 x 158 x 412

31/14

PW9120 BATT 1000

-

-

-

Standard
Connector

-

9.6 x 6.2 x 16.2/
243 x 158 x 412

44/20

PW9120 BATT 1500

-

-

-

Standard
Connector

-

10.8 x 6.7 x 17.5/
275 x 170 x 444

57/26

PW9120 BATT 2000

-

-

-

Standard
Connector

-

14.2 x 8.6 x 18.6/
361 x 217 x 472

110/50

PW9120 BATT 3000

-

-

-

Standard
Connector

-

14.2 x 8.6 x 18.6/
361 x 217 x 472

110/50

1 Also user-selectable for 100, 110, and 127 Vac.
2 Automatic frequency selection.
3 120V models have 6-ft. attached line cord. 230 V models have 6-ft. detachable line cord.
4 Divided into 2 Load Segments (receptacle groups).
5 Also user-selectable for 220 and 240 Vac

Go to top

Battery Run Times (in minutes full load/half load)

VA Standard
Internal
Battery
1 EBM 2 EBMs 3 EBMs 4 EBMs 5 EBMs
700

7/18

34/70

64/140

-

-

-

1000

7/18

36/80

66/155

-

-

-

1500

7/18

29/67

56/130

-

-

-

2000

12/34

49/107

93/195

140/310

192/403

240/504

3000

6/15

30/70

57/128

87/191

120/264

148/325

Up to 2 EBMs can be connected to 700/1000/1500 VA models and up to 5 EBMs can be connected to 2000/3000 VA models.Run time chart provides typical information.Run times are approximate and may vary with equipment,configuration,battery age,temperature,etc.  

 

Available Options

Order Number Description
IPK-0329 ConnectUPS-BD SNMP/WEB Card
1014018 AS/400 Relay Card
E-mail this page Print this page
Copyright ©2008 Eaton Corporation.
All rights reserved.