Electrical Input  1000-2200 VA 2400-3000 VA 
Nominal Voltage 120, 208 and 230 Vac;
 See Model Selection Guide for user-selectable voltages
120, 208, 230 and 240 Vac;
See Model Selection Guide for user-selectable voltages
Input Voltage Ranges (for user-selectable voltages) Low voltage: 77-152 V; High voltage: 154-288 V
Operating Frequency 50/60 Hz, Auto-sensing
Frequency Range 46-65 Hz
Electrical Output
On Utility Voltage Regulation -10% to +6% of nominal
On Battery Voltage Regulation  ±5% RMS
Voltage Wave Shape (on battery)  Sine Wave
Output Protection  Short circuit protection
Battery
Battery Type Sealed, lead-acid; maintenance free
Battery Run time  See Battery Run Times Table
Battery Replacement Hot-swappable internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery Allows start of UPS without utility input
General
Diagnostics Full System self-test on power up
UPS Bypass No Bypass, Internal Bypass
Transfer Time 2-4ms typical
Dimensions and Weights  See Model Selection Guide
Overload (normal operation) 110% overload, shutdown after 3 minutes.
 150% overload, shut down 10 cycles
110% overload for 30 seconds short circuit protected
Communications
User Interface Front Control Panel
Audible Alarms For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault
Network Transient Protector  UL 497 A, in/out jacks RJ45 (high voltage models network protection) &
 RJ11  (low voltage models modem protection)
X-Slot Interface  RS-232 Single Serial Card (standard),
other options available: See available Options Chart
Cable 6-foot communications cable included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
Environmental 
Safety Certifications  UL; cUL; NOM; C-Tick; CE mark
EMC Compliance FCC Part 15, EN50091-2, Class A for 2.2 KVA and RM; Class B for 1000 and 1500 VA tower models FCC Part 15, EN50091-2, Class A
Operating Temperature  0 to 40º C (32 to 104º F)
Storage Temperature -15 to 50º C (5 to 122º F)
Relative Humidity 0% to 95% non-condensing
Lightning & Surge Protection  ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating 480 Joules
Audible Noise Less than 40 dBA typical
 Altitude  3000m (10,000 ft) without derating
Note: Specifications are subject to change without notice due to continuing product improvement programs.

Go to top

Model Selection Guide

Model
Number1
Power 
Rating (VA/Watt)
Input/
Output Voltage
(Vac)2
Input Connection Output Receptacles4 Dimensions HxWxD (in/mm) Weight (lb/kg)
Tower Models (North America)
PW5125
1000
1000/700 120 5-15P,
6 ft line cord
(6) 5-15R 9.45 x 6.38 x 15.79/
240 x 162 x 401
34.3/15.6
PW5125
1500
1440/1050 120 5-15P,
6 ft line cord
(6) 5-15R 9.84 x 6.38 x 18.39/
250 x 162 x 467
50.7/23.0
PW5125
2200
 1920/1600  120 5-20P,
6 ft line cord
 (6) 5-15R,
(2) 5-20R
9.84 x 8.07 x 19.41/
250 x 205 x 493
68.3/31.0
PW5125
2200b
2080/1600 208 IEC-320-15A,
inlet3
(9) IEC-320-10A
(C13)
9.84 x 8.07 x 19.41/
250 x 205 x 493
68.3/31.0
Tower Models (International)
PW5125
1000i
1000/700 230 IEC-320-10A,
inlet3
(6) IEC-320-10A
(C13)
9.45 x 6.38 x 15.79/
240 x 162 x 401
34.3/15.6
PW5125
1500i
1500/1050 230 IEC-320-10A,
inlet3
(6) IEC-320-10A
(C13)
9.84 x 6.38 x 18.39/
250 x 162 x 467
50.7/23.0
PW5125
2200i
2200/1600  230 IEC-320-10A,
inlet3
(9) IEC-320-10A
(C13)
9.84 x 8.07 x 19.41/
250 x 205 x 493
68.3/31.0
Two-in-One Form Factor Models5 (North America)
PW5125
1000 RM
1000/900 120 5-15P,
6 ft line cord
(6) 5-15R 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
1500 RM
1440/1340 120 5-15P,
6 ft line cord
(6) 5-15R 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
2400 RM
2400/2250   120 L5-30P,
(12' attached)
 (1) L5-30R,
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000 RM 
2880/2700 120 L5-30P,
(12' attached) 
(1) L5-30R,
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
Two-in-One Form Factor Models5 (International)
PW5125
1000i RM 
1000/900  230 IEC-320-10A,
inlet3
(6) IEC-320-10A (C13) 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
1500i RM
1500/1340  230 IEC-320-10A,
inlet3
(6) IEC-320-10A (C13) 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
2400i RM
2400/2250  230 IEC-309 16A P,
(12' attached) 
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000g RM
3000/2700 200-240 IEC-320-16A,
receptable
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000e RM
3000/2700  230 IEC-320-16A,
receptacle
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000i RM
3000/2700  230 IEC-309 16A P,
(12' attached) 
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40

1. 50/60 automatic frequency selection.
2. 120 V models are 110 V, 120 V, 127 V user-selectable. 230 V models are 220 V, 230 V, 240 V user-selectable. 208 V models are 208 V, 220 V, 230 V, 240 V user-selectable.
3. Includes (2) each IEC interconnect cables.
4. 1000-1500 VA models are divided into (2) Load Segments (receptacle groups). 2200-3000 VA models are divided into (3) Load Segments (receptacle groups). 5000/6000VA models are divided into (2) Load Segments.
5. Unit fits into standard 19-inch racks. Mounting kits are sold separately.

Go to top

Powerware 5125 Battery Run Time Chart (in minutes full load/half load)*

VA Standard Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
Tower Models
1000 5/14 25/60 55/170 83/199 109/228
1500 6/17 33/79 63/146 92/174 120/201
2200 5/14 26/60 55/170 81/198 106/224
Two-in-One Form Factor
1000  7/19 33/68 58/120 82/166 105/214
1500  5/13 23/57 49/161 73/172 96/205
2400  7/19 35/73 60/124 85/177 110/229
3000  5/15 25/61 49/103 69/146 90/190

*Up to 4 EBMs can be connected to 1000-2200 VA models. EBM run times include internal batteries.
Run time chart provides typical information. Battery run times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

 Go to top

Available Options

Order Number Description
05141562-0021 4 post rackmount kit (fits 19-inch racks)
05146726-5501 2 post rackmount kit (fits 19-inch racks)
05146871-5501 3-Slot seismic mounting kit (1000 / 1500 RM models only)
05146875-5501 5-Slot seismic mounting kit (1000 / 1500 RM models only)
05146447-5502 Multi-Server Card
05146508-5501 USB Card
1018460 Relay Card
103002974-5501 ConnectUPS Web/SNMP card
103002510-5501 Modbus Card
103003637-5501 Environmental Monitoring Probe (EMP)
05146519-001 Powerpass Distribution Module (1000/1500 rackmount models only)
05146401-5501 Power Distribution Unit 250 VA 0U form factor. Side cabinet mount (5000/6000 VA)