Eaton Logo, links to the Eaton homepage

Especificações Técnicas do Powerware 5115 (América do Norte)

Guia de Seleção de Modelos
Autonomia da Bateria
Electrical Input
 Voltage 120 and 230 Vac Nominal; see Model Selection Guide for user-selectable voltages
 On Line Voltage Range +20% for nominal voltage at full load
 Nominal Input Frequency 45-65 Hz, 50/60 Hz; auto-sensing
 Input Protection 120 V models: Reset-able circuit breaker
230 V models: AC source overcurrent protection device (required)
 Connection 120 V models: 6 ft. cord w/5-I5P
230 V models: IEC-320, 10A male connector
Electrical Output
 Power Levels  500-1400 VA
 Online Regulation  -10%, +6% of nominal voltage
 On Battery Voltage Regulation  +/-5% of nominal voltage; -10% after low battery warning
 On Battery Frequency Regulation  +/-0.1 Hz of nominal frequency
 Voltage Wave Shape  Sine wave (during normal and battery operation)
 Connections  See Model Selection Guide
 Interconnecting Cords (230V models)  2 ea. IEC-320, 10A
Indicators and Controls
 Front Panel LEDs  Power on, on battery, overload, and battery fault
 Front Panel Buttons  On/Off and alarm silence/self-test
 Communications Port  DB9 female (UPS ships with communications cable); USB Interface Adapter is optional
 Power Factor  500 VA: 0.64
750/1000 VA: 0.67
1400 VA: 0.68
Battery
 Battery Type  Sealed, maintenance-free lead-acid; starved electrolyte
 Battery Description  500 VA: (1) 12 V, 9 Ah
750 VA: (2) 12 V, 7.2 Ah
1000 VA: (2) 12 V, 9 Ah
1400 VA: (3) 12 V, 9 Ah
 Battery Recharge  < 3 hours to 90% capacity
 Battery Runtime  5 minutes minimum; See Battery Runtimes table
 Start-On-Battery  Startup with UPS batteries in absence of utility power
General
 Topology  Line-interactive
 Dimensions and Weight  see Model Selection Guide
 Network Transient Protector  In and out RJ11 jack for telephone/modem protection (120 V models only) or RJ45 for 10Base-T network cable; UL497A tested
Environmental and safety
 Operating Temperature 0oC to 40oC (32oF to 104oF) UL tested at 25oC (77oF)
 Safety Markings  UL, cUL, and CSA; 230V models also CE and TUV
 Safety Conformance  UL 1778, CAN/CSA C22.2, No. 107.1; 230 V models also EN 50091-1-1 and IEC 60950
 EMC Markings  FCC Class B; 230 V models also CE (EN50091-2) and C-Tick
 Surge Suppression  ANSI C62.41 Category A (formerly IEEE 587)
 Immunity  IEC 801-2, -3, -4
 Transit/Storage Temp. -15oC to 55oC (5oF to 131oF)
 Audible Noise  < 45 dBA typical
 Relative Humidity  5-95% non-condensing

* Due to continuing product improvement programs, specifications subject to change without notice

Go to top

 Model Selection Guide

Model Number Power Out (VA/Watts) Input Connection Output Connections Dimensions HxWxD, (in./mm) Unit Weight (lb/kg)
120 VAC1, 60 Hz auto-sensing
PW5115 500 500/320 5-15P (4) 5-15R 7.6x5.9x10.6/193x150x270 17.2/7.8
PW5115 750 750/500 5-15P (4) 5-15R 7.6x5.9x13.2/193x150x335 27.3/12.4
PW5115 1000 1000/670 5-15P (6) 5-15R 15.1x5.9x13.2/380x150x335 27.8/12.6
PW5115 1400 1400/950 5-15P (6) 5-15R 15.1x5.9x15.4/380x150x390 37.0/16.8
230 VAC2, 60 Hz auto-sensing
PW5115 500i 500/320 IEC-320, 10A (4) IEC-320 7.6x5.9x10.6/193x150x270 17.2/7.8
PW5115 750i 750/500 IEC-320, 10A (4) IEC-320 7.6x5.9x13.2/193x150x335 27.3/12.4
PW5115 1000i 1000/670 IEC-320, 10A (6) IEC-320 7.6x5.9x13.2/193x150x335 27.8/12.6
PW5115 1400i 1400/950 IEC-320, 10A (6) IEC-320 7.6x5.9x15.4/193x150x390 37.0/16.8

1 Also user-selectable for 110V via rear panel DIP switches.
2 230 V default; also user-selectable for 220 and 240 V via rear panel DIP switches

Go to top

Battery Run Times (in minutes)

Load PW5115 500(i) PW5115 750(i) PW5115 1000(i) PW 5115 1400(i)
200 VA / 128 W 17 38 41 58
300 VA / 192 W 11 27 28 41
500 VA / 320 W 5 14 15 28
600 VA / 402 W10 9 10 19
750 VA / 503 W   6 8 14
900 VA / 603 W 6 10
1000 VA / 670 W     5 8
1200 VA / 804 W 6
1400 VA / 938 W       5