Powerware 9170+ UPS Technical Specs

Rating 3kVA 6kVA 9kVA 12kVA 15kVA 18kVA
Part number 9170+C030
ASY-0674;
2xASY-0529
9170+C060
2xASY-0674;
4xASY-0529
9170+C060
 3xASY-0674;
 6xASY-0529
9170+C090
4xASY-0674;
8xASY-0529
9170+C120
5xASY-0674;
10xASY-0529
9170+C120
6xASY-0674;
12xASY-0529
Capacity (kVA/kilowatts) 3/2.1 6/4.2 9/6.3 12/8.4 15/10.5 18/12.6
Dimensions WxDxH(mm) 432x645x453 432x645x800 432x645x800 610x724x1194 610x724x1194 610x724x1542
Weight (kg) 101 163 206 282 325 388
Typical runtime Full load/ Half Load 8-10 min
20-25 min
8-10 min
20-25 min
8-10 min
20-25 min
8-10 min
20-25 min
8-10 min
20-25 min
8-10 min
20-25 min
Input Connection Hardwired
Output Connection Hardwired
Operational
Nominal input voltage (Vac) 220/230/240 Vac single phase
Input Voltage Range 176 to 276 VAC
Operating Frequency 50/60 Hz, (3Hz)
Input power factor 0.98
Input current distortion 3% THD
Nominal output voltage 220/230/240 VAC single phase
Output voltage regulation 3% static
Overload capacity 150% for 10 sec (online), 300% for 12 cycles (bypass)
Efficiency 88% with rated non-linear load
User interface
LCD-display Programmable 4 x 20 character backlit LCD, multiple languages (English, French, Spanish, German)
LED UPS on, on battery, alarm
Standard communication ports 2x ommunication adaptor slots (empty)
RS-232 serial DB-9 port plus contact closures
1 x emergency power off input
Optional External battery cabinets; Web/SNMP adaptor; AS/400 relay adaptor;
N+X redundancy; rack mounting kit; floor anchoring kit;
maintenance bypass module, high capacity charger module
Environmental 
Operating Temperature  0 to +40º C
Storage Temperature -20 to +40º C
Altitude  < 3050m
Audible Noise at 1 metre < 50dB
Certification
Quality ISO 9001
Markings CE/UL/CSA (cUL)/TUV/C-Tick
Safety EN 50091-1-1
EMC EN 55022, EN 50091-2, EN6100-3-2, IEC 61000-3-3, C-Tick