Eaton Logo, links to the Eaton homepage

Powerware 5125RM UPS Technical Specs

Battery Runtimes 
Part Number 51251000IRMBLK 51251500IRMBLK 51253000IRMBLK 51256000IRMBLK
Rating 1000VA 1500VA 3000VA 6000VA
Capacity (VA/Watts) 1000/900 1500/1350 3000/2700 6000/5400
Dimensions WxDxH (mm) 432 x 494 x 89 432 x 494 x 89 483 x 622 x 89 445 x 661 x 133
Weight (kg) 27 27 46 73
Typical runtime
(Full load)
7 min 5 min 5 min 5 min
(Half load) 19 min 14 min 15 min 15 min
Input Connection IEC320/10A IEC320/10A IEC320/16A IEC309/32A
Output Connection 6 x IEC320/10A 6 x IEC320/10A 9 x IEC320/10A
1 x IEC320/16A
IEC309/32A
(4) IEC320/16A
(4) IEC320/10A
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input Voltage Range 166-276 VAC
Operating Frequency 50/60 Hz, Auto-sensing
Input power factor Same as load
Nominal output voltage 220/230/240 VAC
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Information Informative LED display
Standard communication ports RS232
Optional SNMP/WEB card, USB card
Environmental 
Operating Temperature  0 to +40º C
Storage Temperature -15 to +55º C
Altitude  < 3000m
Audible Noise at 1 metre < 45dB normal mode
< 50dB battery mode
Certification
Markings CE/UL (1000-1500 VA), CE (3000 & 6000 VA)
Safety EN 50091-1-1 & UL 1778 (1000-1500 VA), EN50091-1-1-1 (3000 & 6000 VA)
EMC  EN 50091-2, EN6100-3-2 (1000 - 3000 VA)

Go to top


Powerware 5125RM   Runtime in Minutes -  Internal batteries (internal batteries + 1 EBM)*

Load VA/W 1000VA 1500VA 3000VA 6000VA
500VA / 450 W 19 (68) 19 (68) 40 (120) 100(300)
1000VA / 900 W 7 (33) 7 (33) 28 (75) 59 (140)
1500VA / 1350 W - 5 (23) 12 (45) 35 (100)
2000VA / 1800 W - - 8 (35) 26 (79)
3000VA / 2700 W - - 5 (25) 15 (49)
4000VA / 3600 W - - - 10 (35)
5000VA / 4500 W - - - 7 (24)
6000VA / 5400 W - - - 5 (19)
E-mail this page Print this page
Copyright ©2008 Eaton Corporation.
All rights reserved.