Eaton Logo, links to the Eaton homepage

Powerware 5115RM UPS Technical Specs

Battery Runtimes
Part Number 51150500iRM 51150750iRM 51151000iRM 51151500iRM
Rating 500VA 750VA 1000VA 1500VA
Capacity (VA/Watts) 500/320 750/520 1000/670 1440/1000
Dimensions WxDxH (mm) 440 x 578 x 44
Weight (kg) 15.9 18.8 18.8 22
Input Connection IEC320/10A
Output Connection 4xIEC320 10A (2 sockets per load segment)
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input voltage range +20/-20% of nominal
Input frequency range 45-65Hz
Operating frequency 50/60Hz auto sensing
Nominal output voltage 220/230/240 Vac (user selectable)
On utility output voltage regulation -10%/+6% of selected nominal Voltage
On battery output voltage regulation +5% RMS
Overload (nominal operation) 110% overload, shutdown after 3 min
150% overload, shutdown after 3 cycles
Battery
Battery type Sealed, lead-acid maintenance free
Recharge time < 3 hours to 90% useable capacity
Start-On-Battery Allow start of UPS without utility power
User interface
LED LED status display; AC Power On, Load Group, Overload, On battery and General Alarm indicators
Standard communication ports 1 x RS232 & 1 x USB Port
Environmental
Operating temperature 0ºC to + 40ºC
Storage temperature -15ºC to + 55ºC
Altitude < 3000m
Altitude noise at 1 metre < 40dB typical
Certification
Markings CE/UL/C-Tick
Safety EN 50091-1-1 & UL 1778
EMC (Class B) EN 50091-2, EN6100-3-2, C-Tick

Powerware 5115RM Battery Run Times (in minutes)

Model | Load (VA) 51150500iRM 51150750iRM 51151000iRM 51151400iRM
200VA/128W 19 37 41 76
300VA/192W 11 25 29 58
500VA/320W 5 13 15 28
600VA/402W - 9 12 21
750VA/503W - 6 8 16
900VA/603W - - 6 11
1000VA/670W - - 5 9
1200VA/804W - - - 8
1440VA/938W - - - 5
E-mail this page Print this page
Copyright ©2008 Eaton Corporation.